Pre-Operation Checklist
Check spray nozzles and make sure orifice is not blocked or worn to excess.
Check water hose for leaks or kinks
Check all connections, fittings, screws and fasteners.
Check that there are enough tablets to completely clean all coils.
Operating Instructions
Normal Coil Cleaning Operation
CAUTION: Turn off electrical power to unit being cleaned and wear appropriate
P.P.E. (Review the CoilShot and CoilShot-HD SDS before usage)
1.
Connect a standard garden hose to the connection at the base of the gun.
Note: Water Pressure must be less than 70 psi and less than 100
o
F.
2.
Install the nozzle at the tip of the gun, turn on the water source, squeeze the
trigger and pre-rinse the coil to be cleaned. Confirm that all of the connections
are tight and that there are no leaks.
3.
Turn the water source off.
4.
Insert the CoilShot or CoilShot HD cleaning tablet into the back of the gun.
Make sure that the latch secures the door.
Note: If using a new tablet from a sealed bag, make sure to reseal the bag to
ensure no moisture gets to unused tablets.
5.
Adjust mixing valve to desired amount of chemical to be applied (see chart on
next page)
6.
Turn the water source back on. Confirm that all of the connections are still
tight and that there are no leaks.
7.
Squeeze the trigger and spray the coil.
8.
Turn off the water supply.
9.