© Published by permission of the copyright owner – DO NOT COPY or TRANSMIT
Installation/Operation Supplement
19
M414881 (EN)
Steam Requirements
Obtain specific steam service pipe sizes from the
steam system supplier or a qualified steam fitter.
●
pipe configurations.
●
When tumbler is on the end of a line of
equipment, extend header at least 1.2 meters
(4 feet) beyond tumbler. Install shut-off valve,
union, check valve and bypass trap at end of line.
If the system has a gravity return to the boiler,
omit trap.
●
Insulate steam supply and return line for safety of
operator and safety while servicing tumbler.
●
Keep tumbler in good working condition. Repair
or replace any worn or defective parts.
NOTE: This manual is only a supplement. Refer to
installation/operation manual for full instructions.
Thermal Oil Prep
It is the responsibility of the customer to install
appropriate coil and heating system for thermal oil
prep models. Alliance Laundry Systems, LLC. is not
responsible for the performance or safety of the
customer installed thermal oil system. To ensure
proper operation, refer to the
Specifications and
Dimensions
section for the BTU input of equivalent
steam models. Thermal oil systems that do not deliver
appropriate BTUs will dry slower. For solenoid valve
wiring connections, refer to the Wiring Diagram
supplied with tumbler.
All system components must have a
8.6 bar (125 psig) working pressure.
Shut-off valves must be installed upstream
of the steam solenoid valve and
downstream of each steam trap so
components can be isolated for
maintenance or emergency purposes.
All components (solenoid valve, traps)
must be supported to minimize loads on
the tumbler steam coil connections.
W701
WARNING
Содержание Drying Tumblers TMB1268C
Страница 2: ......