Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
18
Principles of Operation
Through the HART connection, you are able to perform:
Detector setup
Detector troubleshooting
Detector health and status
For more details, refer to the
HART Manual TM 777030
.
1.4.4 RS-485 Modbus
For more advanced communications, the 40/40M detector has an RS 485
Modbus-compatible output that provides data communication from a
network (up to 247 detectors) to a host computer or universal controller for
central monitoring. This feature allows for reduced installation costs, easy
maintenance, and local or remote diagnostic tools.
1.4.5 Product Certification
The 40/40M Flame Detectors have the following certifications:
ATEX, IECEx, page 18
SIL-2 (TÜV), page 19
Inmetro (UL), page 19
TR CU/EAC, page 20
1.4.6 ATEX, IECEx
The 40/40M Flame Detector is certified to:
ATEX per SIRA 07ATEX1250X and IECEx per IECEx SIR 07.0085X
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96°C Db
(
–55°C ≤ Ta ≤ +75°C)
or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106°C Db
(
–55°C ≤ Ta ≤ +85°C)
The accessories, Tilt Mount P/N 40/40-001, Weather Cover P/N 777163 and
P/N 777268, Duct Mount P/N 777670 and Air Shield P/N 777650 are
included in the approval.
This product is suitable for use in hazardous zones 1 and 2 with IIC gas
group vapors present, and zones 21 and 22 with IIIC dust type present.
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......