![Spectrex SharpEye 40/40M Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/spectrex/sharpeye-40-40m/sharpeye-40-40m_user-manual_1344022020.webp)
Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
20
Performance Considerations
TR CU/EAC
1.4.6.5
The 40/40M Flame Detector is in compliance with the standard TR CU
012/2011 per:
1Ex d e IIC T5 Gb X
Ex tb IIIC T96
°
C Db X
–
55
°
C
≤
Ta
≤
+75
°
C
or
1Ex d e IIC T4 Gb X
Ex tb IIIC T106
°
C Db X
–
55
°
C
≤
Ta
≤
+85
°
C.
For more details, see TR CU certificate No. Т
R CU C-
US.МЮ62.В.04333.
1.5
Performance Considerations
This section describes performance aspects of the 40/40M and includes:
Detection Sensitivity, page 20
Cone of Vision, page 22
False Alarm Prevention, page 26
Visual Indicators, page 27
Output Signals, page 28
Detector Status, page 29
Auxiliary Relay as End-of-Line, page 30
1.5.1 Detection Sensitivity
Detection sensitivity is the maximum distance at which the detector reliably
detects a specific size of fire and typical type of fuel (standard fire).
Standard Fire
1.5.1.1
Defined as a 1ft
2
/0.1m
2
n-heptane pan fire, with maximum wind speed of
6.5ft/sec / 2m/sec.
Sensitivity Ranges
1.5.1.2
The detector has 4 user-selectable sensitivity ranges. For each range there
are 2 response levels.
Warning (Pre-alarm)
Alarm
The detection distance for the Warning level, is approximately 10% higher
than for the Alarm distance.
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......