![Spectrex SHARPEYE 20 Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/spectrex/sharpeye-20/sharpeye-20_user-manual_1344014036.webp)
Mechanical Specifications
36
SharpEye
TM
IR3 Flame Detector User Guide
•
Communications Network:
The detector is equipped with an RS-485 communications link that can
be used in installations with computerized controllers. The
communications protocol is Modbus compatible.
•
This protocol is a standard and widely used.
•
It enables continuous communication between a single-standard
Modbus controller (master device) and a serial network of up to 247
detectors.
•
It enables connection between different types of SPECTREX
detectors or other Modbus devices to the same network.
5.2
Mechanical Specifications
•
Enclosure:
St.St 316L electro chemical and passivation coating.
•
Functional Test:
FM functional test per 3260 for 20/20MI-3 & 20/20MI-1
VdS approval for 20/20MI-1 only
•
Water and dust tight
•
NEMA 250
type 6p
•
IP 66 and IP 67 per EN 60529
•
Electronic Modules
•
Conformal coated
Electrical connection (2 options)
Connector Interface (mating connector supplied with detector)
Cable Interface
•
Dimensions
Base: 4.3
”/
110mm x 3.9
”/
100mm
Height: 2.6
”
/65.5mm
Weight
St. St. 316L Housing
20/20MI-11 With Cable Output
20/20MI-12 With Plug Output
20/20MI-31 With Cable Output
20/20MI-32 with Plug Output
3.3lb/1.5kg
4.2lb/1.9kg
3.3lb/1.5kg
4.2lb/1.9kg
Tilt Mount
0.8 lb/0.37 kg