Spectrex Inc. - SharpEye
TM
Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005
19
E.
Electrical outputs
•
Dry Contact Relays
:
Table 10: Contact Ratings
Relay
Name
Type
Normal
position
Maximum Ratings
Alarm
SPDT
N.O. N.C.
2A at 30VDC or 0.5A at 250 VAC
Accessory
SPST
N.O.
5A at 30VDC or 250 VAC
Fault
SPST
N.C.
5A at 30VDC or 250 VAC
•
4
-20mA Current Output
:
Terminals 11 and 12:
FAULT
< 2mA
(Typical 0)
NORMAL
4 - 6mA
( 5)
WARNING
9 - 11mA
(10)
ALARM
14 –16mA
(15)
•
Communication Network
:
The detector is equipped with an RS-485 communication link that can
be used in installations with computerized controllers.