TM 799200 Rev. (4), April 2017
63
8
Troubleshooting
In this chapter…
page 63
Troubleshooting Problems
8.1
Table 21: Troubleshooting Problems
Problem
Cause
Solution
“Maintenance call”
status or R, S1, and
S2 are below 2.5VDC
at Gain 4
Poor alignment
Perform alignment
Dirt on the
window
Clean the window
Poor light source Replace the light source
Detector fault
Replace/repair detector
NQRat1 and NQRat2
below the permitted
limit
Gas in the path
Make sure that the path is
clean and the weather
conditions are good
NQRat1 and NQRat2
above the permitted
limit
Poor alignment
Perform alignment
R/N, S1/N, S2/N
below 50
Poor alignment
Perform alignment
Dirt on the
window
Clean the window
Poor light source Replace the light source
Detector fault
Replace/repair detector
Temperature higher
than 25°C beyond
the room
temperature
Electronic
problem
Replace/repair detector
Ratio1 and Ratio2 out
of the limit
Poor alignment
Perform alignment
Dirt on the
window
Clean the window
Detector fault
Replace/repair detector
Voltage less than
16VDC. The detector
at “V” fault
Low input
voltage
Check the power supply and
installation