Zero Calibration
58
SafEye
TM
Xenon 700S Gas Detector User Guide
6.5.1
Signal Values Limitation
Table 20 describes the maintenance data channels limitation values.
Table 20: Maintenance Channels Limited Values
Channel
Installation Distance
Maintenance
Min
Med
Max
Reference
1V Gain1
1V Gain2
1V
Gain3
The minimum signal
allowed is 2.5V at Gain 4
Signal 1
1V Gain1
1V Gain2
1V
Gain3
The minimum signal
allowed is 2.5V at Gain 4
Signal 2
1V Gain1
1V Gain2
1V
Gain3
The minimum signal
allowed is 2.5V at Gain 4
Ratio 1
0.6–2
0.6–2
0.6–2
0.5–3
Ratio 2
0.6–2
0.6–2
0.6–2
0.5–3
NQRat 1
0.95–1.05
Must be 0.95–1.05
NQRat 2
0.95–1.05
Must be 0.95–1.05
LEL
0 LEL x m
0 LEL x m
Temp.
Up to 25° C beyond room temp.
Up to 25° C beyond
room temp.
Voltage
32VDC > V > 17VDC
32VDC > V > 17VDC
Ref/Noise
More than 80
More than 30
Sig 1/Noise More than 80
More than 30
Sig 2/Noise More than 80
More than 30
Note
: The installation information refers to the installation distance.
Min
: The minimum distance as defined for that model
Med
: Half of the maximum distance as defined for that model
Max
: The maximum distance as defined for that model
Zero Calibration
6.6
Zero calibration must be performed after:
Installation
Realignment
Window cleaning
Any change in detector or source position
Precise alignment must be performed prior to the zero calibration procedure.
Perform zero calibration in good weather conditions, with insignificant gas
concentrations in the surrounding environment, or indoors.
Содержание SafEye Xenon 700S