Mounting for Duct Installation
52
SafEye
TM
Open Path Detection System User Guide
5.4.8
Detector Terminal Wiring
The detector contains a terminal board consisting of 2 terminal blocks.
5.4.8.1
Power Supply:
The input power is supplied to Terminal 1. The return is connected to
Terminal 2.
Note
:
Ensure that the detector unit receives a minimum of 18VDC and
does not exceed 32VDC.
5.4.8.2
Fault Relay:
The fault relay is normally open. The SPST relay is at Terminals 4 and 5.
The contacts are normally energized closed when the detector is in normal
operation.
5.4.8.3
Alarm Relay:
The Alarm Relay is SPDT relay. Terminals 6 and 7 are normally open and
the contacts are closed when the detector is in the alarm status. Terminals
7 and 8 are normally closed and the contacts are open when the detector
is in the alarm status.
5.4.8.4
Accessory Relay:
The Accessory output is normally open SPST relay. Its contacts are at
Terminals 9 and 10. It can be defined per user requirements (see
Appendix B).
Note
:
To protect the dry contacts from voltage surges when connected to
reactive loads (electric motors, sirens, etc.), connect an appropriate
varistor over these contacts.
5.4.8.5
4
–20mA Output
Terminals 11 and 12 are used for 4
–
20mA current output as specified in
on page 24 (see Appendix B).
5.4.8.6
RS-485 Output
Terminal 13 and 14 are used for the communications network (see
Appendix B).
Содержание SafEye 300 Series
Страница 2: ......
Страница 10: ......
Страница 32: ......
Страница 58: ......
Страница 64: ......
Страница 67: ...TM794200 Rev Ad March 2019 67 Appendix B Wiring Option Configurations Figure 13 Detector Wiring Diagram ...
Страница 70: ......
Страница 71: ...TM794200 Rev Ad March 2019 71 Appendix C Outline Drawings ...
Страница 72: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......