Output Signals
24
SafEye
TM
Open Path Detection System User Guide
Table 3: Alignment Indication LED Color
Left LED
Right LED
Gain
Red
Red
3
Orange
Orange
2
Green
Orange
1
Green
Green
0
2
After 20 minutes at alignment mode the detector will return to normal mode.
3
After zero calibration is finished, the detector will return to normal mode and
the signal intensity will be saved for next alignment comparison.
4
The 4
–
20mA level in this table refers to discrete indication option. A different
(continuous reading) option is described later in
page 24.
3.7
Output Signals
The SafEye system provides the following outputs:
•
Standard 4
–
20mA port
•
Three dry contact relays
•
Optional RS-485 output for PC communications
3.7.1
4
–20mA Current Output
The 4
–
20mA output can provide the detector status measurement in 1 of
the 2 following methods:
•
It can be measured proportionally (default) showing a continuous
reading of the exact gas concentration (see Table 4).
•
It can be a discrete indication according to the detector mode or the
warning or alarm signal at a defined gas concentration. Setting of this
method can be done by a maintenance host or PC unit.
The 4
–
20mA functions as the current source. The maximum permitted
load resistance for the 4
–
20mA output is 600ohms. The minimum
permitted load resistance is 100ohms.
Содержание SafEye 300 Series
Страница 2: ......
Страница 10: ......
Страница 32: ......
Страница 58: ......
Страница 64: ......
Страница 67: ...TM794200 Rev Ad March 2019 67 Appendix B Wiring Option Configurations Figure 13 Detector Wiring Diagram ...
Страница 70: ......
Страница 71: ...TM794200 Rev Ad March 2019 71 Appendix C Outline Drawings ...
Страница 72: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......