12V DC Wire Gauge and Transmission 

Distance Reference 

The recommended max transmission distance is under the following environments: The 
wire diameter is fixed and the DC 12V power voltage loss rate is below 10%. For the device 
being supplied the DC power, the max allowed voltage loss rate is 10%. All the wires listed in 
the following sheet are copper wire. (Copper wire resistance

ρ = 0.0175Ω ∗ mm

/m

 

   mm 

Feet

m

 

w        

0.8000 

1.000 

1.250 

2.000 

122.13

37.23

 

190.83

58.16

 

298.17

90.88

 

763.31

232.66

 

10 

61.06

18.61

 

95.41

29.08

 

149.08

45.44

 

381.66

116.33

 

15 

40.71

12.41

 

63.61

19.39

  99.39

30.29

 

254.44

77.55

 

20 

30.53

9.31

 

47.71

14.54

  74.54

22.72

 

190.83

58.16

 

25 

24.43

7.45

 

38.17

11.63

  59.63

18.18

 

152.66

46.53

 

30 

20.35

6.20

 

31.80

9.69

 

49.69

15.15

 

127.22

38.78

 

35 

17.45

5.32

 

27.26

8.31

 

42.60

12.98

 

109.04

33.24

 

40 

15.27

4.65

 

23.85

7.27

 

37.27

11.36

  95.41

29.08

 

45 

13.57

4.14

 

21.20

6.46

 

33.13

10.10

  84.81

28.85

 

50 

12.21

3.72

 

19.08

5.82

 

29.82

9.09

 

76.33

23.27

 

55 

11.10

3.38

 

17.35

5.29

 

27.11

8.26

 

69.39

21.15

 

60 

10.18

3.10

 

15.90

4.85

 

24.85

7.57

 

63.61

19.39

 

65 

9.39

2.86

 

14.68

4.47

 

22.94

6.99

 

58.72

17.90

 

70 

8.72

2.66

 

13.63

4.15

 

21.30

6.49

 

54.52

16.62

 

75 

8.14

2.48

 

12.72

3.88

 

19.88

6.06

 

50.89

15.51

 

80 

7.63

2.33

 

11.93

3.64

 

18.64

5.68

 

47.71

14.54

 

85 

7.18

2.19

 

11.23

3.42

 

17.54

5.35

 

44.90

13.69

 

90 

6.78

2.07

 

10.60

3.23

 

16.56

5.05

 

42.41

12.93

 

95 

6.43

1.96

 

10.04

3.06

 

15.69

4.78

 

40.17

12.25

 

100 

6.11

1.86

 

9.54

2.91

 

14.91

4.54

 

38.17

11.63

 

 

Содержание O2P12XH

Страница 1: ...Quick Start Guide 12X PTZ IP Camera O2P12XH Version 1 1 1...

Страница 2: ...nstallation 2 2 2 Wall Mount Installation Steps 2 2 2 1 Installation Environments 2 2 2 2 Installation Steps 2 3 IP SCANNER 5 3 1 Overview 5 3 2 Operation 5 4 WEB OPERATION 6 4 1 Login and Main Interf...

Страница 3: ...This manual is designed to be a reference tool for your system Please read this manual carefully before operating the unit and retain it for future reference Should you require any technical assistan...

Страница 4: ...iquid intrusion into the camera 3 Operation and Daily Maintenance Please shut down the device and then unplug the power cable before you begin any maintenance work Do not touch the CMOS sensor optic c...

Страница 5: ...t manuals and specifications may be modified without prior notice Speco Technologies reserves the right to modify these without notice and without incurring any obligation Speco Technologies is not li...

Страница 6: ...ial requirement please contact your local dealer for more information We assume no liability or responsibility for all the fires or electrical shock caused by improper handling or installation 1 2 Che...

Страница 7: ...ries 2 2 2 Installation Steps 1 Drill a hole of 50mm diameter for the cable exit in the installation wall 2 In Figure 2 2 connect the adapter block to the internal thread of the wall mount bracket unt...

Страница 8: ...he bottom of the wall mount bracket Please make sure the cable exit of the bracket is facing the round hole on the wall Connect the cable and then pull it through the hole in the wall Use four hex scr...

Страница 9: ...4 Now the installation is complete See Figure 2 4 Figure 2 4...

Страница 10: ...nd double click to open up the web viewer 5 IP Scanner can search for the device on the local network Please note that only devices that are on the same subnet can be discovered In the device list you...

Страница 11: ...hange the password after initial login 6 This device supports viewing and management via a web browser on a PC Login and Main Interface twork camera address in the address bar or double click the Figu...

Страница 12: ...earth Open floor cable layout should not be used In areas prone to strong thunderstorms or near high sensitive voltage such as near high voltage transformer substation you need to install additional h...

Страница 13: ...31 47 71 14 54 74 54 22 72 190 83 58 16 25 24 43 7 45 38 17 11 63 59 63 18 18 152 66 46 53 30 20 35 6 20 31 80 9 69 49 69 15 15 127 22 38 78 35 17 45 5 32 27 26 8 31 42 60 12 98 109 04 33 24 40 15 27...

Страница 14: ...0 0 130 36 39 0 01327 0 140 35 0 01539 0 160 34 37 0 02011 0 180 33 0 02545 0 200 32 35 0 03142 0 230 31 0 04115 0 250 30 33 0 04909 0 290 29 31 0 06605 0 330 28 30 0 08553 0 350 27 29 0 09621 0 400 2...

Отзывы: