Specified Controls SC-Z20 Скачать руководство пользователя страница 3

SC-Z20

MODULATING ZONE CONTROL SYSTEM

OVERVIEW

The SC-Z20 is a commercial zone control system that allows a single HVAC unit to have up to 20
individual zones. Each zone is controlled by its own space thermostat and a modulating damper.
When a majority of zones are calling for cooling, the system operates in the cooling mode. The SC-
Z20 controls up to two stages of cooling to maintain a cooling discharge air setpoint. If a majority of
zones are calling for heating, the system changes from the cooling mode to the heating mode. The
SC-Z20 then controls up to two stages of heating to maintain a heating discharge air setpoint. When
the number of heating and cooling requests are equal, the system satisfies the cooling request first.

SEQUENCE OF OPERATION

The SC-Z20 controls the system fan, two stages of cooling and two stages of heating. In the
occupied mode, the fan runs continuously. Cooling stages are cycled to maintain a discharge air
temperature of approximately 54° F. Heating stages are cycled to maintain a discharge air
temperature of approximately 140° F. The control panel is equipped with two slide switches
designated “

” used to increase the number of zones that must be calling before the

Minimum Calls

equipment will come on. All stages of heating and cooling have a five minute minimum ON/OFF time.
There is also a ten minute time delay between first and second stage. The system will remain in
whatever mode it is in for a minimum of fifteen minutes. If equal heating and cooling calls take place,
cooling will receive priority. Equipment mode of operation is based on a “Majority Wins” control
algorithm.

UNOCCUPIED MODE

The panel has a set of clock terminals “ ” for occupied and unoccupied scheduling. When the clock

T

terminals are open, the system is placed in the unoccupied mode. All stages of heating or cooling are
turned off and the fan shuts off after a five minute delay. See wiring and programming instruction in
this manual for the SC-Z20-NS Night Stat.

WARNING

1. Turn power off to HVAC unit and control panel during installation to prevent serious injury from

electrical shock and/or damage to the system.

2. Use extreme care when making duct openings and handling sheet metal to avoid injury.
3. The SC-Z20 panel and all components must be installed in a conditioned space where the

ambient temperature will not exceed 150° F.

4. Install all components in a manner that provides access for test, check and startup.

CAUTION

1. Installation of this system must be in compliance with all applicable codes.
2. HVAC system must be properly sized and balanced to assure optimum system performance.
3. A bypass damper must be installed to maintain proper system static pressure.
4. All low voltage wire must be 18 gauge.
5. All wiring should be color coded and tagged for proper identification.
6. When landing wires to the control panel, zone thermostats and actuator boards, make sure wires

are snug, but do not over-tighten screw terminals.

Содержание SC-Z20

Страница 1: ...SC Z20 Commercial Zone Control System Modulating or Two position Installation Manual...

Страница 2: ...Works with single stage multi stage or heat pump systems No programming required Auxiliary heat control option for each zone Night setback option All low voltage wiring LEDs indicates status of equipm...

Страница 3: ...second stage The system will remain in whatever mode it is in for a minimum of fifteen minutes If equal heating and cooling calls take place cooling will receive priority Equipment mode of operation i...

Страница 4: ...SC Z20 MODULATING ZONE CONTROL SYSTEM WIRING AND LAYOUT GUIDE 3 SC Z20 NS NIGHT STAT SC Z20...

Страница 5: ...OOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE STATUS HEAT COOL DAS ACTIVE OCCUPI...

Страница 6: ...on Zones 1 20 RED Heat ON when there is a call for heating GREEN Cool ON when there is a call for cooling HVAC System W1 GREEN ON when first stage heat is energized W2 GREEN ON when second stage heat...

Страница 7: ...T COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE TIME DELAYS DIVIDED BY 15 STATU...

Страница 8: ...AT Insert a small flat bladed screw driver in the release slot located on the bottom of the thermostat and pry straight up and away from the subbase Avoid twisting the case as this may stress the LCD...

Страница 9: ...rge air temperature at the damper is below 72 degrees the zone damper will open on a call for cooling SC Z20 PANEL NOTES Use standard 18 gauge thermostat wire Run four wire cable from the panel termin...

Страница 10: ...S DS HEAT COOL WIRE TO OPTIONAL SLAVE DAMPER UP TO 20 MAY BE WIRED IN PARALLEL SC Z20 T AUTO CHANGEOVER SPACE THERMOSTAT FACTORY JUMPER RED LED INDICATES A CALL FOR HEATING GREEN LED INDICATES A CALL...

Страница 11: ...t T terminals on the SC Z20 panel that places the system in the occupied or unoccupied mode of operation The thermostat can also be used with a SC T32 S1 Indoor Remote Sensor 24 volt power to the ther...

Страница 12: ...HE CLOCK AND DAY OF WEEK It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time 1 Touch the until the day of the week flashes T...

Страница 13: ...ram to additional days of the Program CPY week use the or arrow to add additional days Example UP DOWN Mon Tue Wed Thu Fri 13 Once you have selected the days to be copied touch will begin to flash and...

Страница 14: ...hat the HVAC equipment have two stages of heating and two stages of cooling The pressure drop through the zone dampers is negligible and should not be a factor when sizing branch duct runs Zone damper...

Страница 15: ...e from each zone damper Connect terminals and R C Y W R C Y W from each zone damper to the terminals labeled and on the interface board 18 4 thermostat wire is recommended SC Z20 NS PROGRAMMABLE NIGHT...

Страница 16: ...discharge air setpoint If the number of zones calling for heating and cooling are equal the system will operate in the cooling mode first This is known as Cooling Priority Each zone damper or diffuse...

Страница 17: ...ol shall be required for setup and not troubleshooting B The zone control panel shall be suitable for the indoor ambient Environment conditions and shall be rated for operation between 32 F and 120 F...

Страница 18: ...nected to the output shaft 2 All actuators shall be factory wired to the damper control board 3 All damper actuators shall be mounted outside of the air stream B The damper actuator control board shal...

Страница 19: ...ermostat wire 18 gauge minimum No shielded cable shall be required 3 Control wire and cable shall be installed in accordance with NEC 1 06 SERVICE AND GUARANTEE A The entire zone control system shall...

Отзывы: