CHECKING GAS PRESSURE
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the fireplace, STOP! Do not install the
appliance. Contact your dealer immediately.
1
/
2
" gas line onto shut-off valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
fireplace for leaks. Use a solution of 50/50 water and
soap or a gas sniffer.
4.
Figure 34 - Gas Pressure Check at Gas Valve
Do not use open flame to check for gas leaks.
WARNING
FAN ASSEMBLY DIAGRAMS
Speed Control Control Shaft
Control
Knob
Switch
Bracket
Blower
Plug-In
Duplex Outlet
(Located underneath
firebox floor against
Blower Location
Side View
Strips
Exhaust Port
Screw
Green
Ground
Wire
Spade
Terminals
Lower Firebox Cavity
FR
ONT
BA
CK
(see page 5)
BLOWER/FAN LOCATION
Outlet Pressure Tap
Pilot Adjustment
Inlet Pressure Tap
lower right outside wall, as shown on page 5)
Velcro
2. T
o
ease installation, a 30" flex line with manual
shut-off valve has been provided with on this appliance.
Install and attach
To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
See
Figure 34.
After taking pressure reading, be sure and turn
captured screw clockwise firmly to reseal. Do not over
torque. Check test points for gas leaks.
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in ex-
5
. The appliance and its appliance main gas valve must be
cess of 1/2 psi (3.5 kPa). The appliance must be isolated
from the gas supply piping system by closing its equipment
shutoff valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2 psi
(3.5 kPa)
.