SpaGuts VS300FC5 Скачать руководство пользователя страница 2

Installation P/N 73-200-0300, Rev. A, 9/04/2015 

Note: For 110V systems, the heater will only operate when the pump is running on low speed. When the pump is on high speed, the heater 
will not operate until the high speed turns off. 

*220V Power Supply, 60Hz 

*Minimum 50A Power Supply is required. Use Copper Conductors Only. See wiring diagram for more information. 

Please note that this Installation requires 4 dedicated wire connections to the power  terminal block (TB1) on the Circuit Board. These 
include 

Line 1

Line 2

Neutral

 and 

Ground

. Connect Line 1 wire to Line 1 terminal. Connect Line 2 wire to Line 2 terminal. Connect 

Neutral wire to Neutral terminal. If a dedicated Neutral wire is not connected, the heater will never come on and/or the system will not 
operate properly. Lastly, connect Ground to the Grounding Bar located on the side of the controller box. Since this system is not equipped 
with  a  GFCI,  it  is  REQUIRED  by  the  National  Electric  Code  to  install  an  external  GFCI  for  safety  and  protection. Any  mis-wiring  or 
improper installation will void the warranty and could cause personal injury, death, fire or property damage.

 

Do  Not  follow  the  color  of  the  original  power  wires,  Black,  Red, White  and  Green.    DON'T ASSUME THESE WIRES ARE WIRED 
ACCORDING TO  LOCAL  CODES.  Some  original  wirings  can  have  the  wires  mixed  up.  Get  a  voltage  meter  and  verify  each  wire  to 
make sure which colored wire is Line 1, Neutral, and Ground.  Failure to do so will cause major electrical damage to the controller and/or 
other equipment, and void the warranty. 

DO NOT POWER UP THE SPA UNLESS THE SYSTEM IS COMPLETELY INSTALLED AND THE SPA IS COMPLETELY FILLED 
UP WITH WATER. Doing so can cause a dry fire, which can damage the heater and controller, and will void the warranty. 

Primary Pump Circuit:  

The primary pump circuit should have already been configured for the correct voltage output based on your 

order for “Factory Configured”. For “Field Configurable Kit” or if you find out that the pump motor is rated at a different voltage, make 
sure to configure pump 1 circuit to the correct voltage for the pump motor by following the wiring diagram that is provided. 

Pump Motor wiring:

 The primary pump cord will have 4 wires for two speed operation. This system utilize the RED wire for High-

Speed and the BLACK wire for Low-speed in Two-Speed Pump Circuits. The White wire is for Line/Common connection, and the Green 
wire is for ground. Keep this in mind when connecting a Two-Speed pump that has not been purchased with this system. If using a single 
speed pump as the primary pump, cap off the RED wire. Connect the primary pump cord in Pump 1 location (J23) on the circuit board. 
The plug will only fit one way. Make sure the clip on the plug latches to ensure tight connection. If a complete Spa Pack with pump was 
ordered, the pump cord should have already been connected. 

Ozone Circuit:

 The ozone circuit should have already been configured for the correct voltage output based on your order for “Factory 

Configured”. For “Field Configurable Kit” or if you find out that the ozone unit is rated at a different voltage, make sure to configure the 
ozone circuit to the correct voltage for the ozone unit by following the wiring diagram that is provided. 

Ozone wiring:

 The ozone cord will have 3 wires. The Black wire is for Line 1. The White wire is for Common connection, and the Green 

wire is for ground. Connect the ozone cord in the Ozone location (J29) on the circuit board. The plug will only fit one way. Make sure the 
clip on the plug latches to ensure tight connection. Only connect the ozone cord if it is being used. 

Circulation Pump Circuit:

 NOT available on this system.

 

Dip Switch Settings:

 The dip switches on the circuit board (as known as Switch Bank A, red in color with white switches) should have 

already  been  configured  for  the  correct  setting  based  on  your  order  for  “Factory  Configured”.  For  “Field  Configurable  Kit”  or  if  a 
different setup is required, the dip switches need to be configured. If so, please follow the dip switch settings based on the new setup by 
using the wiring diagram as a reference. 

Topside Panel Installation

: A hole cut out of 3.75 inch x 1.0 inch is required for the SpaGuts Topside Panel, P/N 50553. A topside cover 

plate (included) can be used if the existing hole cut out is larger than the topside panel. Clean the surface area before installation of the 
new topside panel. Position the topside panel in the direction for operational purpose as desired. Then carefully insert the topside cable 
through  the  hole  cut  out.  Remove  the  protective  label  from  the  sticky  gasket  on  the  back  of  the  topside  panel. Then  apply  the  topside 
panel above the hole cut out or cover plate. Silicone can be used under the lip of the topside panel for additional water leak protection 
prior to installation of the topside panel. Connect the topside cable plug into J1 connector on the circuit board. The clip on the topside 
cable plug should snap in place to ensure a secure connection. Note that this control system does not allow a secondary topside panel or 
an auxiliary topside panel connection. If a longer topside cable is needed, DO NOT splice the cable or disconnect the cable from the back 
of the topside panel to install a longer cable. Doing so will affect the proper functionality of the topside panel and completely void the 
topside warranty. Available at  www.spaguts.com is P/N 30311 for the 10ft extension cable, and P/N 22639 for the 25ft extension cable. 
Maximum cable length is 50ft in order for the topside panel to work properly. 

Light wiring:

 The light harness is 8ft long with 2 wires. One end of the light harness has a 2-prong amp plug, and the other end has a 

light  socket  that  fits  a  12V  12W  light  bulb  or  a  ColorGlo  Led  Light  (http://www.spaguts.com/Products/colorglo-led-lights-47.aspx). 
Connect the 2-prong amp plug in location (J20) on the circuit board. The plug will only fit one way. Make sure the clip on the plug latches 
to  ensure  tight  connection.  Insert  the  light  bulb into  the  light  socket. Then  insert  the  light  socket  with  light  bulb  into  the  existing  light 
housing on the spa. The white light reflector can also be used if it fits in the existing light housing. If a light housing is not installed, it can  
be purchased by going to this link: http://www.spaguts.com/Products/thru-shell-light-lense-kit-88.aspx. Only connect the light harness if it 
is being used. 

Audio Video wiring (A/V):

 NOT available on this system. 

Отзывы: