19

FIGURE 2.27: SIDE BRANCH

Spacepak Air 

Handler 

7” RND w/70% of Total Outlets 

A & B 

F  G 

9” RND 

7”

 R

N

D

 w

/3

0%

 o

f T

ot

al 

O

ut

le

ts 

C & D 

A: Minimum distance from the air handler outlet to first tee or elbow is 18” 
B: No outlets in the first 18” of straight pipe off of the air handler 
C: Minimum distance of straight pipe a!er any tee or elbow is 18” 
D: Minimum distance when placing outlet a!er any tee or elbow is 18” 
E: Minimum distance between outlets is 6” on center 
F: Minimum distance when placing an outlet from the end cap is 12” 
G: Never place an outlet in the end cap 

9” Tee 

DESIGN RULES FOR RETRO-

FITTING “B&C” SERIES SPACEPAK 

EQUIPMENT TO NEWER 

(D,E,F,G,J) SERIES EQUIPMENT 

SECTION 3: START-UP & OPERATION 

SEQUENCE OF OPERATION

When power is turned on and thermostat fan switch is 

set  to  ON  and  the  cooling  indicator  is  set  to  OFF,  the

indoor fan motor is energized through the normally open

contact FR-1 of the FR fan relay in about 30 seconds.

The outdoor unit is off.

When power is turned on and thermostat fan switch is 

set to ON or AUTO and the cooling indicator to COOL 

the  indoor  and  outdoor  units  will  start  through  the 

normally  open  contacts  FR-1  and  FR-2  of  the  FR  fan

relay.

The fan coil unit is equipped with a primary float switch, 

the outdoor unit will automatically shut down if the drain

pan is full of water (condensate) and not draining. The 

fan coil unit will continue to operate, when the water level in

the drain pan drops, the system will continue normal

operation.

PRIOR TO START-UP   

1. Check all electrical connections for tightness.

2. Check air filter has been installed in return air box or 

filter box.

3. Remove all winter supply shut-offs and store them in 

a safe place.

SYSTEM START-UP & ADJUSTMENTS

1. Place thermostat fan switch in ON position and cool-

ing  indicator  in  OFF  position.  In  about  2  minutes,

indoor unit blower will start.

2. Check blower operation for excess noise or vibration.

3. Check entire distribution system for leakage and apply

additional tape where necessary.

4. Measure/adjust blower voltage/speeds

a. Remove the control box cover located on the side 

of the unit.

b. With the unit powered and operating from a 

conventional thermostat, ensure there is no conditioning

call (Thermostat is satisfied) and switch the fan 

control to “Manual” or “On” to create a G call.

NOTE:  IF NO AIRFLOW DURING W OR Y CALL,

POTENTIOMETER MAY  BE  IN  “OFF”  POSITION.

TURN CW TO ACHIEVE AIRFLOW

c. Place the ground/neutral probe in the lower right hole 

marked “COM” and the volt probe in the hole marked 

“Flo0” (for fan only, G call) and measure DC volts between

0 and 5V. Adjust the potentiometer adjacent to the “Flo0”

to achieve the desired volt reading. Repeat for remaining

adjustments marked Flo1 through Flo4 as indicated on 

the label inside the cover. (Refer to Figure 3)

Содержание WCSP-2430J

Страница 1: ...ies Retrofits 17 19 SECTION 3 START UP OPERATION Sequence Of Operation 19 Prior To Start Up 19 System Start Up Adjustments 19 Operating Setpoints 21 23 Factors Affecting the Balance of the System 24 S...

Страница 2: ...ur as a result of overflow from the equipment drain pan or stoppage in the condensate drain piping from a cooling or an evaporator coil AIR DISTRIBUTION SYSTEM COMPONENT REQUIREMENTS Air distribution...

Страница 3: ...tains a specified amount of sound attenuating tubes kwik connects terminator plates incl spring clips screws winter supply air shut offs and a balancing orifice set to complete installation of room ou...

Страница 4: ...3 not more than 30 of the total number of system outlets should be attached to the perpendicular branch of the tee The larger system capacities WCSP 3642 4860 are affected more by higher system static...

Страница 5: ...bration isolation pads a condensate trap assembly and a factory installed primary float switch AA AA ROOM TERMINATOR FIGURE 1 4 TERMINATOR IN SOFFIT AREA AA AAAAA AAA AAA AAAAA AAAAA AAAA SUPPLY TUBIN...

Страница 6: ...J WCSP 4860J 2 2 1 2 3 3 1 2 4 5 440 550 3 4 3 4 3 4 5 6 2 8 7 6 4 10 6 5 4 6 6 6 2 4 105 123 144 660 850 880 1150 2 4 2 4 Coil Wheel Dia 115V 230V and Width 10 x 6 10 x 6 10 x 6 Bottom Top FIGURE 2 2...

Страница 7: ...5 0 50 0 55 0 60 0 65 0 70 0 75 0 80 0 85 0 90 0 4 0 5 0 6 0 7 0 8 0 9 0 Water Flow Rate GPM Heating Capacity MBH 160 EWT 140 EWT 120 EWT WCSP 3642 850 cfm Heating Capacity 30 0 35 0 40 0 45 0 50 0 55...

Страница 8: ...box should fit between successive joists Where joists run in the opposite direction or to properly center the return it may be necessary to cut joists and install headers For all wall return applicat...

Страница 9: ...attic A HORIZONTAL DISCHARGE Refer to Figure 2 7 and duct installation instruc tions supplied with fan coil unit 14 5 16 FIGURE 2 6 RETURN AIR BOx FRAME DIMENSIONS Measure return air box dimension A t...

Страница 10: ...ides for servicing For installations with a return air box and return air duct set fan coil unit on the platform with the elliptical opening facing in the direction of the return air opening The suppl...

Страница 11: ...ndensate line to a closed drain system Step 6 Installing the Condensate Trap Line ITEM 1 2 3 4 5 6 MALE ADAPTER 3 4 DESCRIPTION ELBOW 45 3 4 1 2 PLUG 3 4 X 1 2 BUSHING TEE 3 4 P TRAP 3 4 3 4 P TRAP AS...

Страница 12: ...12 FIGURE 2 11 MODEL WCSP J 230V STANDARD WIRING SCHEMATIC For 115V conversion instructions see conversion kit supplied separately with the unit...

Страница 13: ...F Heating Water Coil Present Heating Water Coil Settings Switch 2 No Heating Water Coil Present Energized in Cooling Mode Changeover Valve Settings Switch 4 Energized in Heating Mode ON Fan Circulatio...

Страница 14: ...S WITH THICKER WALL 3 16 GAP FOR APPLICATIONS WITH THICKER WALLBOARD 3 16 GAP FOR APPLICATIONS WITH THICKER WALLBOARD 3 16 GAP FOR APPLICATIONS WITH THICKER WALLBOARD 3 16 GAP FOR APPLICATIONS WITH TH...

Страница 15: ...tube Third thread kwik connect into the inner core until snug Fourth pull the insulation and cover for ward and tuck it into the deep groove on the back side of the kwik connect Fifth wrap the connect...

Страница 16: ...19 TAKE OFF INSTALLATION PLENUM FASTENER GASKET PLENUM TAKE OFF GASKET PLENUM TAKE OFF PLENUM FASTENER 1 HAND INSERT FASTENER INTO PLENUM TAKE OFF 2 WITH PLIERS SNAP FASTENER INTO PLACE UNTIL IT LOCKS...

Страница 17: ...tical flange on the fan coil unit see Figure 2 23 Move the clamp over the flange and tighten so the clamp holds the return air duct securely to the flange Follow the same procedures to attach the retu...

Страница 18: ...HOE LAYOUT Spacepak Air Handler 9 RND 7 RND w 60 or 50 of Total Outlets A B F G A Minimum distance from the air handler outlet to rst tee or elbow is 18 B No outlets in the rst 18 of straight pipe o o...

Страница 19: ...if the drain pan is full of water condensate and not draining The fan coil unit will continue to operate when the water level in the drain pan drops the system will continue normal operation PRIOR TO...

Страница 20: ...o that the end is approximately flush with the inside wall of the plenum and perpendicular to the direction of airflow 3 System static pressure should be between 1 2 and 1 5 WC a If the pressure is hi...

Страница 21: ...5VDC 2 0VDC 1 7VDC 1 4VDC 1 0VDC SystemCurves Nominal operating point 550 CFM at 1 2 ESP 5 0V 4 5V 4 0V 3 5V 3 0V 2 5V 2 0V 1 5V 1 0V 2 2 475 380 2 0 638 547 455 260 1 8 680 640 600 485 370 1 6 830 7...

Страница 22: ...t 850 CFM at 1 2 ESP Curves 5 0V 4 5V 4 0V 3 5V 3 0V 2 5V 2 0V 1 5V 1 0V 2 2 520 2 0 730 635 540 460 380 1 8 860 795 730 640 550 410 1 6 970 910 850 800 695 550 360 1 5 1 020 965 910 830 740 610 430 1...

Страница 23: ...ingpoint 1 150 CFM at1 2 ESP 5 0V 4 5V 4 0V 3 5V 3 0V 2 5V 2 0V 1 5V 1 0V 2 2 520 2 0 760 728 695 625 1 8 920 885 850 800 630 1 6 1 040 1 005 970 900 760 585 1 5 1 100 1 060 1 020 950 810 650 400 1 4...

Страница 24: ...ATION 5 65 85 1 00 1 15 1 30 1 50 1 65 1 70 1 80 1 85 1 95 1 5 1 35 1 15 1 1 5 1 35 2 35 1 35 1 15 or 1 1 5 or 3 5 1 1 35 or 2 5 1 35 2 15 2 35 1 5 1 1 15 3 35 2 00 2 For a room with more than two 2 t...

Страница 25: ...th 2 Check fan coil unit Turn off unit power disconnect switch and remove service access panels a Inspect coil and blower wheel for build up of dust and dirt Clean with solvent and or water as necessa...

Страница 26: ...of coil WG SpacePak Motor Amps measured Amps Voltage measured Volts Air Temperatures Return indoor ambient FDB FWB Condensing unit outdoor ambient F AHU read 3 ft from fan discharge F last supply outl...

Страница 27: ...s W09RWG0422 01 8 Electrical Control Box Cover All Sizes 462RWG0529 J1 9 Side Access Panel Coil Side All Sizes 462RWG0527 01 10 Primary Float Switch All Sizes 455RWG0543 02 11 Cable Connector Ground A...

Страница 28: ...o the Manufacturer of that part of the Product thought to be defective Goods can only be returned with prior written approval from the Manufacturer All returns must be freight prepaid b determination...

Отзывы: