41357080
July 06
2
This heater is for INDOOR INSTALLATION ONLY. While the products of combustion are expelled into the building,
national codes require ventilation in the building to dilute these products of combustion. This ventilation may be
provided by gravity or mechanical means. Refer to Section 8 of this manual for minimum requirements for ventilation
and combustion air.
Copies of the National Fuel Gas Code (ANSI Z223.1 - latest edition) are available from the American Gas Association
Laboratories, 8501 E. Pleasant Valley Road, Cleveland, OH 44131. All NFPA codes are available from the National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
NOTE: This heater does not comply with Section 2.10 Radiant Coefficient of ANSI Z83.6 (latest edition)
WARNING: DO NOT move, handle or service a hot or operating heater.
WARNING: Heaters must only be used on stable and level surfaces for safe operation.
2. SPECIFICATIONS
MODEL NO.
GAS TYPE
INPUT BTU/HR
ORIFICE SIZE
RFPA21A-N6
RFPA21A-L6
NATURAL
PROPANE
212,000
200,000
"H" (.2660)
#20 (.1610)
Gas Pipe connection:
½" NPT Female
MODEL SUFFIXES:
N - Natural Gas
L - Propane Gas
6 - Standing Pilot Ignition
100% Safety Shutoff, Manual Valve (Baso)
DIMENSIONS
RFPA21A
HEATER
PACKAGED
SHIPPING WEIGHTS
18-1/2" x 18-1/2" x 51-1/2"
62 LBS.