3.4

Ventilation

The installation room should have a volume of at least 10m

3

/kw of installed nominal heat input of the

radiant heater.

The ventilation requirements and calculation methods for unflued appliances are set out in the
European Standard 

EN 13410:2001

 and must be applied.  The following is guidance to the standard:

Ventilation may be achieved by any of the three following different means:

a) thermal evacuation of the products of combustion/air mixture
b) mechanical evacuation of the products of combustion/air mixture
c) natural air change
 

3.4.1.1 Ventilation by Thermal Evacuation

Ventilation by thermal evacuation is sufficient if 

10m

3

/h of exhaust air per kW of operating heat

input

 are ventilated out of the installation room.

The air/products of combustion mixture must be evacuated above the radiant heaters, if possible near
the ridge, by means of exhaust mixture opening(s), (vents).

Where the exhaust mixture opening(s) can be closed, it shall only be possible to operate the radiant
heaters when they are open.

The maximum horizontal distance between a radiant heater and a vent opening shall be:

6 (six) times the vent height in the case of 

wall

 openings

3 (three) times the vent height in the case of 

roof

 openings

3.4.1.2 Ventilation by Mechanical Evacuation

Ventilation by mechanical evacuation is sufficient if 

10m

3

/h of exhaust air per kW of operating heat

input

 are ventilated out of the installation room.

The air/products of combustion mixture must be evacuated above the radiant heaters using fan(s).

It shall only be possible to operate the radiant heaters whilst the exhaust airflow is proven.

The maximum horizontal distance between a radiant heater and a fan shall be:

6 (six) times the fan mounting height in the case of 

wall

 openings

3 (three) times the fan mounting height in the case of 

roof

 openings

Total minimum proven ventilation airflow in 

m

3

/h 

will be:

Total installed kW input X 10 

Note:

Mechanical exhaust air openings must be positioned such that the burner stability of the
nearest appliance is unaffected.

3.4.1.3 Ventilation by Natural Air Change

Gas-fired radiant heaters may be operated without any special exhaust system if the exhaust gases
are discharged to the outside atmosphere by a sufficient natural air change in the installation room.

Furthermore, no provision for thermal or mechanical ventilation is required in the following particular
cases:

buildings with natural air change greater than 1.5 volumes per hour

buildings with a density of operating heat input not greater than 5W/m

3

 

Содержание ERP10

Страница 1: ...P SERIES MODELS ERP10 ERP20 ERP30 ERP40 ERP45 Gas Fired Products UK Ltd Chapel Lane Claydon Ipswich Suffolk IP6 0JL England Tel 01473 830551 Fax 01473 832055 E mail Info spaceray co uk www spaceray co...

Страница 2: ......

Страница 3: ...3 Checking Gas Pressure 12 5 4 Flame Supervision 12 6 Servicing 13 14 6 1 Ignition Electrode 13 6 2 Flame Sensor Probe 13 6 3 Venturi 13 6 4 Injector 13 6 5 Electrical Wiring 13 6 6 Reflector 14 7 Re...

Страница 4: ...90kW Hs 17 43kW Hi Appliance Type A1 Appliance Cat II2H3P Gas Rate 1 96m 3 h 1 36kg h Adjusted For 2H G20 20mbar 3P G31 37mbar Setting Pressure 15 0mbar 25 0mbar Injector 2 x No 41 2 x No 52 Pre Injec...

Страница 5: ...2 Pre Injector None None Electrical Supply 230V 50Hz 25W Fuse Externally 3A Dimensions L 0 673m W 0 848m H 0 197m Weight 20 36kg Gas Connection Rc Table 5 MODEL ERP45 N Heat Input 46 89kW Hs 42 25kW H...

Страница 6: ...and suitable brackets are used Attach the chains or drop rods to the 4 holes located in the Side Frame Panels as shown in Fig 1 by use of M8 screws and nuts Providing at least 5mm closed link hooks a...

Страница 7: ...Page 5 of 20 Fig 1 Disclaimer Valve and control assemblies will differ on European approved heaters...

Страница 8: ...used and the pipework must be designed to achieve a gas supply pressure between the maximum and minimum valves stated above measured at the appliance inlet pressure test point A union service cock MUS...

Страница 9: ...H 1 SWITCH 1 THERMOSTAT Fig 3 Notes The method of connection to the electrical supply must facilitate complete isolation and should preferably be via a fused double pole isolator having a constant sep...

Страница 10: ...ET PLUG BASE ERP 10 20 30 40 45 SIDE FRAME PANEL VALVE G Y 3 3 5 Internal Wiring Diagram S I T Controls Fig 5 Fig 4 N L1 BK G Y BL BR 121110 9 8 7 6 5 4 3 2 1 G Y BL BR BL HT GR G Y 4 PIN BASE PLUG TE...

Страница 11: ...penings 3 three times the vent height in the case of roof openings 3 4 1 2 Ventilation by Mechanical Evacuation Ventilation by mechanical evacuation is sufficient if 10m3 h of exhaust air per kW of op...

Страница 12: ...ed to junction box attached to the Control Valve as follows Brown to terminal marked 1 Blue to terminal marked 2 Green Yellow to terminal marked 7 External fuse required 3 A See section 3 3 for electr...

Страница 13: ...lenoid valve and ignition spark electrode will be de energised and the appliance Ignition Control will go to lockout condition 5 1 7 To repeat the ignition sequence it will be necessary to switch off...

Страница 14: ...or below the Control Valve Category 2H gas type G20 natural setting pressure 15 0mbar Category 3P gas type G31 propane setting pressure 25 0mbar 5 3 2 3 In the event that the burner setting pressure i...

Страница 15: ...y oxidised replace the electrode see section 7 1 6 1 4 Upon re assembly ensure that the HT lead connector is securely attached to the electrode 6 2 Flame Sensor Probe 6 2 1 Disconnect the grey flame s...

Страница 16: ...probe by gently pulling the connector using pliers 7 2 2 Unscrew the two M4 screws securing the flame probe to the Side Frame Panel RH and withdraw the flame probe 7 2 3 After assembling a replacemen...

Страница 17: ...located in the elbow flange and straight flange connectors are in sound condition and correctly positioned in the O ring grooves of the connectors 7 7 Reverberatory Screen 7 7 1 Remove the wire ties f...

Страница 18: ...Injector No 52 LPG 4262 8 OPERATING INSTRUCTIONS 8 1 Direct Burner Spark Ignition Models 8 1 1 Turn on the gas supply to the appliance 8 1 2 Set any time switch or thermostats to demand heat 8 1 3 Swi...

Страница 19: ...n using LPG that the reverberatory screen is fitted 9 2 Conversion from cat 2H Natural Gas to cat 3P LPG Appliance with reverberatory screen 9 2 1 Carry out the instructions 9 1 1 to 9 1 4 above leavi...

Страница 20: ...Rectify Gas Supply to the appliance Gas Setting pressure in accordance with section 3 2 of manual Is Ignition spark present at Electrodes Does Ignition Spark cease when Burner ignites NO NO NO Adjust...

Страница 21: ...NOTES Page 19 of 20...

Страница 22: ...Page 20 of 20 09 03 GB 602S...

Отзывы: