INDOOR INSTALLATION
–
HANGING METHODS
12.2)
When the heater is used for an Indoor Installation then the following hanging methods may be used.
The heater can be hung from the ceiling, secondary steel work, etc. using chains, threaded rods and other approved
hanging materials. All hanging materials must have a minimum working load of 52kg. Any “S” hooks must be
crimped closed after installation.
Note:
When hanging the heater hanging materials which allow the heater to move the gas connection must be
established using an approved flexible gas hose of a minimum of 600mm length.
Diagram below shows Horizontal mounting with chain.
Diagram below shows the possible chain methods to hang at different angles.
Notes: When suspending at 25 degrees if the heat shield is installed use the 30-degree location for the heat shield.
INDOOR / OUTDOOR RIGID HANGING BRACKETS
12.3)
Fixed hanging methods which prevent the heater from swaying must be used for outdoor installations.
Below are the bracket kits which can be used for ceiling and wall mount for patio heaters installed indoors and
outdoors, with and without heat shields. The brackets provide for a range of lengths and approved mounting angles
of 15
0
, 30
0
, 45
0
and 60
0
.
44560350
KIT, BRACKET - WALL/CEILING 380-560mm CEILING - FOR USE WITH HEAT SHIELD (telescoping)
44560351
KIT, BRACKET - CEILING 560-760mm - FOR USE WITHOUT HEAT SHIELD (telescoping)
44560353
KIT, BRACKET - CEILING 10" – FIXED (For Horizontal mounting with a heat shield - non-combustible
ceiling only)