Form 44201360
14
Oct 2019
TYPICAL HEATER LAYOUTS
8.0)
The diagram below shows the recommended spacing layout between heaters.
Dimension
Horizontal
15 to 30 degree angle
Above 30 degree angle
Min.
Max.
Min.
Max.
Min.
Max.
A. Mounting Height
2.4m
3.4m
2.15m
2.7m
2.15m
2.4m
B. Distance to the end of the
patio
0m
1.8m
0m
1.8m
0m
1.8m
C. Distance between heaters.
2.4m
3.7m
2.15m
3.4m
1.8m
3.0m
D. Distance between heaters*
2.4m
4.9m
2.4m
5.5m
2.4m
4.9m
*Note the distance D for angled heaters applies when they are facing towards each other.
Below are examples of patio heating applications.