FOR SMOKE DETECTORS 

1. Remove paper backing from mounting template from 

detector kit and affix to the air duct at desired location. 

2. Using the template as a guide, drill or punch (2) 1-1/4” dia. 

holes in the air duct, for the sampling tube/exhaust tube. 

3. Position the SSU-WP-2000-SE enclosure in such a way that 

the holes (on the template and SSU-WP-2000-SE) are lined 
up with each other. 

4. Mark the (4) SSU-WP-2000-SE air duct mounting holes. 

Then drill (4) 3/32” (2.5mm) pilot holes as marked. 

5. Secure SSU-WP-2000-SE enclosure to the duct with (4) #12 

x 3/4” sheet metal screws (SSU-WP-2000-SE kit). 

6. Fit the duct smoke detector into the 1-1/4” holes on the air 

duct. 

7. Secure the duct detector with sheet metal screws (from 

detector kit) to the SSU-WP-2000-SE enclosure. 

8. Connect sampling tube/exhaust tube to the duct detector 

(position the sampling tube in such a way that air flows into 
the intake holes). 

PRODUCT SPECIFICATIONS 

USE: 

SL Series duct smoke detectors 
System Sensor DNR duct smoke detector 

CONDUIT KNOCKOUTS: 

On bottom: 3 convertible 0.875” 

MATERIAL: 

16ga SST white painted finish 

FRONT ACCESS: 

Removable Cover with two screws 

HARDWARE: 

Enclosure mounting screws, ground screw kit, and tube vent kit included 

PROTECTION RATING: 

Type 1 and Type 3R – UL 50 and CSA 
Outdoor: Internal equipment protected from falling rain, etc: undamaged by ice formation 

ENVIRONMENTAL: 

See appropriate duct smoke detector specifications 

APPROVALS: 

UL: BGUZ.E257104 
CUL: BGUX7.E257104 

MOUNTING 

CAUTION: 

DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE 

 

INSTALLING VENT TUBES 

1. Punch out (2) .875” knockouts. 
2. Feed vent tube (side without tab) through vent tube 

holder and larger side of grommet, as shown, until vent 
tube is flush with grommet. (make sure vent tube tab lines 
up with slot on vent tube holder) 

3. Feed same side through open knockout. 
4. Use mount plate, (2) #6 lock washers, and (2) 6-32 screws 

to hold vent tube in place, make sure tube vent is up 
against mount plate, and tab of vent tube is pointing 
inwards before tightening. 

 