background image

SSU-WP-2000

 

WEATHERPROOF ENCLOSURE FOR 

SMOKE DETECTORS 

1. Remove paper backing from mounting template from 

detector kit and affix to the air duct at desired 
location. 

2. Using the template as a guide, drill or punch (2) 1-1/4” 

dia. holes in the air duct, for the sampling 
tube/exhaust tube. 

3. Position the SSU-WP-2000 enclosure in such a way 

that the holes (on the template and SSU-WP-2000) are 
lined up with each other. 

4. Mark the (4) SSU-WP-2000 air duct mounting holes. 

Then drill (4) 3/32” (2.5mm) pilot holes as marked. 

5. Secure SSU-WP-2000 enclosure to the duct with (4) 

#12 x 3/4” sheet metal screws (SSU-WP-2000 kit). 

6. Fit the duct smoke detector into the 1-1/4” holes on 

the air duct. 

7. Secure the duct detector with (2) sheet metal screws 

(from detector kit) to the SSU-WP-2000 enclosure. 

8. Connect sampling tube/exhaust tube to the duct 

detector (position the sampling tube in such a way 
that air flows into the intake holes). 

PRODUCT SPECIFICATIONS 

USE: 

SL series duct smoke detectors 
System Sensor DNR duct smoke detector 

CONDUIT KNOCKOUTS: 

On bottom: 3 convertible 0.875” 

MATERIAL: 

16ga CRS white painted finish 

FRONT ACCESS: 

Removable Cover with two screws 

HARDWARE: 

Enclosure mounting screws and ground screw kit included 

PROTECTION RATING: 

Type 1 and Type 3R – UL 50 and CSA 
Outdoor: Internal equipment protected from falling rain, etc: undamaged by ice formation 

ENVIRONMENTAL: 

See appropriate duct smoke detector specifications 

APPROVALS: 

UL: BGUZ.E257104 
CUL: BGUX7.E257104 

MOUNTING 

SPACE AGE ELECTRONICS                          1SAE.COM                         800-486-1723                     EC0151                 REV. A 

CAUTION:

 DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE

 