15
5. CONTROL OF ORKA
5.1. INSTALLATION
5.1a. Airfl ow selection
The equipment has 2 confi gurations (A and B) for low speed depending on the connection (see chapter 4). The peak
airfl ow (high speed) function is common to both confi gurations.
Peak
5.1b. Alarm change fi lters
The unit has a timer “12 months TIMER S&P” that alerts the user when to change the fi lters. It is a movable device
and must be located where the user can view the alarm status.
Pilot
Button
The alarm is timed to activate at 12 months. Once this time has elapsed, the pilot will light up every 10 seconds during
the fi rst 4 days. Subsequently, the fl ashing will be every 30 seconds for the next 9 days.
When the fi lters have been changed, the alarm must be reactivated by pressing the button for 5 seconds.
To check the remaining time until the end of the timing, press the button for 3 seconds and the pilot light will illumi-
nate a number of times to the number of months remaining to reach 12 months.
To confi rm that the battery has suffi cient charge, press the button (<1 second) and the pilot light will illuminate once.
If not, the battery should be replaced with a new one. The remaining time for the alarm activation is saved.
The battery life for normal use is approximately 3 years.
The battery is CR2032 type.
Remove the battery protection for activation.