16 Doors IP Control Panel

              

Factory Reset

Reset Button:

Step1:

 

After powering on the device, please firstly connect 

Fire

 contact on 

CN15

 to 

GND

 Ground. 

Step2:

 

Press

RESET

button on the main board for more than 5 seconds till the BUSY LED  is 

            blinking ,release

RESET

button. 

Step3: 

After reset, the device will automatically restart and the IP address will be changed back

            to default value : 192.168.1.127 

Step4: 

Disconnect 

Fire

 contact on 

CN15

 from 

GND

 Ground.

When the controller is connected to the power, [POWER] will turn on green LED; if there is no 

light, it means the power supply has some problems.

POWER LED 

※ 

If you do not perform "Flash Restoring", but the [RESET] and [BUSY] has been 

blinking in red, that indicates a PCB problem should be excluded.

When the red LED is lit, the memory is being cleared and restored to the factory default action.

BUSY LED

RS-485 Connection: HOST RX & HOST TX LED

Remarks: LED Description

[HOST RX] : When receiving incoming data from the host PC, the green LED will keep blinking

[HOST TX] : When transmitting the data back to the host PC, the red LED will be blinking

a

b

c

d

e

f

Remarks:

 

WG0: Node ID fixed to 17 while connected and Fixed to trigger 

the K1 Relay

WG1: Node ID fixed to 18 while connected and Fixed to trigger 

the K2 Relay
CH1: RS-485 Reader Node ID must be set up from 03 to 08
CH2: RS-485 Reader Node ID must be set up as 09 to 16