V220613
- 6 -
16 Doors IP Control Panel
Factory Reset
Reset Button:
Step1:
After powering on the device, please firstly connect
Fire
contact on
CN15
to
GND
Ground.
Step2:
Press
【
RESET
】
button on the main board for more than 5 seconds till the BUSY LED is
blinking ,release
【
RESET
】
button.
Step3:
After reset, the device will automatically restart and the IP address will be changed back
to default value : 192.168.1.127
Step4:
Disconnect
Fire
contact on
CN15
from
GND
Ground.
When the controller is connected to the power, [POWER] will turn on green LED; if there is no
light, it means the power supply has some problems.
POWER LED
※
If you do not perform "Flash Restoring", but the [RESET] and [BUSY] has been
blinking in red, that indicates a PCB problem should be excluded.
When the red LED is lit, the memory is being cleared and restored to the factory default action.
BUSY LED
RS-485 Connection: HOST RX & HOST TX LED
Remarks: LED Description
[HOST RX] : When receiving incoming data from the host PC, the green LED will keep blinking
[HOST TX] : When transmitting the data back to the host PC, the red LED will be blinking
a
b
c
d
e
f
Remarks:
WG0: Node ID fixed to 17 while connected and Fixed to trigger
the K1 Relay
WG1: Node ID fixed to 18 while connected and Fixed to trigger
the K2 Relay
CH1: RS-485 Reader Node ID must be set up from 03 to 08
CH2: RS-485 Reader Node ID must be set up as 09 to 16