15
Operation cont.
Battery Replacement
1. When the battery is depleted, the symbol will appear on the LCD display.
Replace the battery immediately.
2. Use a small flat bladed screwdriver to loosen the one screw.
3. Remove the battery cover.
4. Replace the battery with
one 9 volt battery.
5. Install the battery cover
and tighten the screw.
To avoid electric shock, do not operate the meter
until the battery cover is securely fastened to the meter.
WARNING:
To avoid electric shock, remove the test leads from
the meter before removing the battery cover.
WARNINGS:
screw
16
Specifications
6.000V
60.00V
600.0V
1000V
Input Protection:
1000V AC rms or 1000V DC
AC voltage bandwidth:
50 to 60Hz, True RMS response
1mV
10mV
0.1V
1V
±(1.5% +5 digits)
±(1.5% +5 digits)
±(1.5% +5 digits)
±(3.0% +8 digits)
AC Voltage
(Autoranging)
Function
Range
Resolution
Accuracy
±
(
% of r digits)
600.0mV
6.000V
60.00V
600.0V
1000V
Input Protection:
1000V DC or 1000V AC rms
All AC voltage ranges are specified from 5% to 100% of range.
0.1mV
1mV
10mV
0.1V
1V
±(1.0% +20 digits)
±(1.2% +3 digits)
±(1.2% +3 digits)
±(1.2% +3 digits)
±(1.5% +3 digits)
DC Voltage
(Autoranging)
Function
Range
Resolution
Accuracy
±
(
% of r digits)
600.0
Ω
6.000k
Ω
60.00k
Ω
600.0k
Ω
6.000M
Ω
60.00M
Ω
Input Protection:
600V DC or 600V AC rms
0.1
Ω
1
Ω
10
Ω
100
Ω
1k
Ω
10k
Ω
±(1% +4 digits)
±(1.5% +2 digits)
±(1.5% +2 digits)
±(1.5% +2 digits)
±(2.0% +5 digits)
±(3% +8 digits)
Resistance
(Autoranging)
Function
Range
Resolution
Accuracy
±
(
% of r digits)
60.00A
600.0A
1000A
Maximum Input:
1000A AC rms or 1000A DC
AC current bandwidth:
50 to 60Hz, True RMS response
All AC current ranges are specified from 5% to 100% of range
All AC voltage ranges are specified from 5% to 100% of range
10mA
0.1A
1A
±(2.5% +8 digits)
±(2.5% +8 digits)
±(3.0% +3 digits)
AC Current (50/60Hz)
Function
Range
Resolution
Accuracy
±
(
% of r digits)