Page 14 of 22
Installation & Adjustment Procedures
Operating Mechanism
Figure 12: Typical Operating Mechanism
1. Lay out all Operating Mechanism parts and check them against the Op-Mech drawing bill-of-
materials.
2. To ensure that the bearing stops do not interfere with switch adjustments, loosen all open/close
bearing stops, and slide them out of the way.
3. Refer to the Operating Mechanism drawing, and install all mounting brackets, bearings,
bushings, pipe clevises, switch operating device, adjustable arm, reach rod, and other
necessary components. Refer to
4. While installing the pipes and clevises that have piercing bolts/set screws, do not pierce the
pipe until instructed. Tighten the piercing bolts such that they grip the pipe until all adjustments
are made.
The pipe collar (above the vertical bearing) must support the entire weight of the
vertical operating pipe. To prevent unnecessary component damage,
do not allow
the pipe to rest on the switch operating device.
Refer to
A – Motor or Manual Operator
B – Vertical Pipe
C – Vertical Bearing
D – Pipe Collar
E – Adjustable Arm
F – Pipe Clevis
G – Reach Rod
H – Interphase Pipe
J – Switch Arm
(See Operating mechanism drawings provided for details)
Содержание EC-2V
Страница 1: ...TYPE EC 2V Aluminum Center Break Vee Disconnect Switch ALL Ratings INSTRUCTION INSTALLATION MANUAL...
Страница 2: ...Page I The Quality Name in High Voltage Switching THIS PAGE LEFT INTENTIONALLY BLANK...
Страница 6: ...Page V The Quality Name in High Voltage Switching THIS PAGE LEFT INTENTIONALLY BLANK...
Страница 7: ...Page VI The Quality Name in High Voltage Switching Type EC 2V...
Страница 31: ...Page 22 of 22 Recommended Inspection Maintenance Comments...