FPS-900 O&M Manual 
Revision: 2; 7/2020 

Page 5 of 29 
 

2.  Safety Guidelines 

 
The following section outlines the basic safety considerations about installation and operation of the 

N

2

-

BLAST

 ®

 FPS-900. For other equipment used with the nitrogen generator, such as air compressors, and 

dryers, refer to the manufacturer’s safety guidelin

es. 

 
2.1  General 

 
Using the 

N

2

-BLAST

®

 FPS-900 correctly is important for safety and trouble-free operation. Wrong use 

can cause damages to the system or can lead to incorrect gas supply. The nitrogen generator produces 
nitrogen at a low flow rate, which quickly dissipates into the air. Nitrogen is not poisonous, but do not 
directly inhale, since high concentrations, can cause asphyxiation.  
 

Warning: Install the unit in a well-ventilated room, one that is sealed off from normal living space 
air changes.

 

 

Read carefully and act accordingly before installing, operating, or repairing the unit: 
 

  The operator must use safe working practices and rules when running the nitrogen generator. 

  The owner is responsible for always keeping the unit in safe working conditions. 

  Always use approved parts when performing maintenance and repairs. Make sure that replacement 

parts meet or exceed the original parts’ specification.

 

  Only competent individuals, train and authorized, can install, operate, perform maintenance and 

repair.   

  Isolate incoming and outgoing pressures to the generator, and depressurize the service or repair 

section before performing any mechanical work, including changing the filters. Vent the nitrogen 

generator’s exhaust gas outside or to a large, well

-ventilated room to avoid suffocation due to lack 

of oxygen. 

 

 

  Wear safety glasses if the cabinet door is open while the machine is running. 

 

  Use ear protection when the equipment is running. 

 

WARNING: Components may experience pressure during operation. Pressurized gases are 
dangerous and may cause injury or death if handled or used inappropriately. 

 

 

Never allow pressurized gas to exhaust from an unsecured hose. An unsecured hose may 
present a whipping action, which can cause serious injury. If a hose burst during use, 
immediately close all isolation valves if safe and turn off the unit.  

 

Never disable or bypass any safety relief valves. 

 

Always disconnect the nitrogen generator the supply power prior to performing electrical 
work. 

 

NOTE: Always follow local and site safety regulations in conjunction with this manual. Correct use of the 
nitrogen generator is important for personal safety. Incorrect safety practices can cause damage to the 
individual and equipment.  

 

Содержание N2Blast FPS-900

Страница 1: ...The Leader in Nitrogen Generation Technology FPS 900 Fire Protection Systems O M Manual Version 2 7 2020 2020...

Страница 2: ...4 3 Electrical Requirements 4 4 Site Specifications 5 PRODUCT INSTALLATION 9 5 1 Mounting 5 2 Installation Arrangement 5 3 Panel Layout and Gas Connections 6 SYSTEM DESIGN 13 6 1 Key Features 6 2 Spec...

Страница 3: ...designing nitrogen generators for worldwide distribution Why not produce nitrogen at your facility for a fraction of the cost versus endlessly paying for bulk liquid or delivered gas cylinders We mak...

Страница 4: ...e repair or replacement of such and in no event shall seller be liable for incidental consequential or punitive damages resulting from any such cause Seller shall not be liable for and Buyer assumes a...

Страница 5: ...rs Make sure that replacement parts meet or exceed the original parts specification Only competent individuals train and authorized can install operate perform maintenance and repair Isolate incoming...

Страница 6: ...Read the manual before installing and operating the nitrogen generator to prevent accidents and damages Contact the supplier for questions not answered in this manual Only use the FPS 900 for its desi...

Страница 7: ...mate controlled 60 80 F room Always keep N2 BLAST in an upright position or preferably in the box as shipped Read entire manual and make all connections per instructions before connecting power Keep a...

Страница 8: ...nt is greater than 50 feet consult with a piping contractor for proper line size 4 3 Electrical Requirements The N2 BLAST FPS 900 requires 120VAC 50 60hz 1ph and draws 8A 240VAC is also available thou...

Страница 9: ...LAST FPS 900 first with the provided bolts lock nuts 4 Optional If wall studs are not 16 center to center reinforce the mounting area with a 1 2 or thicker plywood prior to hanging the system Use best...

Страница 10: ...sult in bodily harm or damage to the system as well as voiding the system s warranty Item STS Part Description QTY 1 TYP1P UNIT TYP1P Unit Shown 1 2 800 133 S 100 200 Mounting Bracket 1 3 800 134 B TY...

Страница 11: ...d connections Item STS Part Description QTY 1 800 111 FPS 100 Red Tank with Label 1 2 A01 0100 A Tank Strap Assembly 1 3 A01 0100 S A Tank Manifold with 0 500 Nozzles 1 Should this handle be in the cl...

Страница 12: ...3 Audible Electrical Buzzer Audible Alarm 4 0 100 PSIG Pressure Gauge N2 Storage Tank Pressure Gauge 5 PLC System Controller 6 OD Through wall Coupling OD Drain 7 NPT Way Ball Valve AIR BYPASS TOP 8...

Страница 13: ...o filters between the compressed air and O2 separation beds the particulate and coalescing The 5 micron particulate filter catches the bulk particles and the 0 1 micron coalescing catches the remainin...

Страница 14: ...signal can be an audible visual and dry contact connection to the Building Management System BMS Power cycle the unit to reset the alarm but avoid doing this multiple times without finding the cause...

Страница 15: ...the major control functions and instrumentations associated with the nitrogen generators All programs are proprietary and password protected from the factory Do not alter any controls or instrumentat...

Страница 16: ...it is active Note resetting this will also trigger the Customer Alarm Relay for one second Blastoff Simulation Hold the Set Button for 7 seconds Passcode Screen will pop up 1 Press the Set Button one...

Страница 17: ...manual bypass mode by turning the handle on the left side of the cabinet With the handle in the Bypass Mode the bypass alarm triggers an audible and visual alarm Air n2 bypass on the screen A dry cont...

Страница 18: ...below Function Data Type Modbus RTU Address Units Status Read Write Running Standby BOOL 00012 0 Standby 1 Running R Common Alarm BOOL 00004 1 Good 0 Alarm R BlastOff Alarm BOOL 00015 0 Good 1 Alarm...

Страница 19: ...ng the Up and Down buttons 3 Press the ENT Button to confirm the entry It will bring Hold Set Screen press NEXT button to get to the analog output screen 4 20 out Using the up and down buttons buttons...

Страница 20: ...power connection is correct 3 Turn the 3 way ball valve on the generator s left side to the Nitrogen Out position 4 Open the inlet ball valve on the nitrogen storage tank 5 Close the outlet ball valv...

Страница 21: ...oss Consult with your installer if you cannot find the leakage area 8 2 1 To determine if the leak is between the Generator and the Nitrogen Tank 1 With the unit powered on close off both ball valves...

Страница 22: ...n off the unit and open the front cabinet door 2 Locate the air filters on the bracket in the middle of the cabinet See Figure 7 3 Make sure the filters are completely depressurized by checking the pr...

Страница 23: ...P The Leader in Nitrogen Generation Technology FPS 900 O M Manual Revision 2 7 2020 Page 23 of 29 Figure 7 FPS 900 Filter locations Particulate Filter Coalescing Filter Air in Pre Filter...

Страница 24: ...tions about the performance and or maintenance of the system They will be best suited to answer your questions and your quickest solution on any issues you may have If they cannot be reached contact t...

Страница 25: ...andby Mode When the pressure drops by about 7 10 psig the system should go into Run Mode and begin to refill the storage If you are out specifications we need to determine where the issue is Contact t...

Страница 26: ...add set points and alarms to trace the oxygen content in system and maintain the purity of the nitrogen gas There is two sensor options for this feature Max O2 100 Range sensor O2 PCENT PPM Trace Par...

Страница 27: ...P The Leader in Nitrogen Generation Technology FPS 900 O M Manual Revision 2 7 2020 Page 27 of 29 Figure 7 Setting screens Flow Diagram...

Страница 28: ...ction Data Type Modbus RTU Address Units Status Read Write High oxygen Alarm Percent BOOL 00108 0 Good 1 Alarm R High oxygen Alarm PPM BOOL 00117 0 Good 1 Alarm R Pressure cut in Double integer 40144...

Страница 29: ...anged to a different specification at the factory s option Any work performed by an unauthorized person company or usage of non factory parts may void all warranties to the product Any item not manufa...