OWNER'S MANUAL

About Advanced Features & Operation

CYCLES PER HOUR - The Cycles Per Hour setting (

page 16)

 monitors the 

     number of times per hour your HVAC unit may energize.  For example,
     at a setting of 6 cycles per hour the HVAC unit will only be allowed to 
     energize once every 10 minutes.  The Cycles Per Hour limit may be 
     temporarily overridden by pressing the WARMER or COOLER button.
      
DEADBAND OPERATION - Controls up to two Heat and two Cool stages.
    

and

   The 

2nd Stage

 of heat or cool is turned on when:

      (

A

) The 1st Stage has been on for a minimum of 

two minutes

.

   
      (

B

) The temperature spread from the setpoint is equal to or greater

            than: 

the setpoint plus the 1st stage deadband (page 14), plus

            the 2nd stage deadband.  

This 2nd stage deadband is fixed at

            two degrees and is not adjustable.      

                  

   The 

1st Stage

 of heat or cool is turned on when:

      (

A

) The temperature spread from the setpoint is equal to or greater than:

             

the setpoint plus the 1st stage deadband (page 14)

.  This 1st stage dead-

             band is adjustable from 1-6 degrees and the default is two degrees. 

Heat

Setpoint

Cool

Setpoint

Deadband

Deadband

db 1

1st Stage

turn on

2nd Stage

turn on

1st Stage

turn on

2nd Stage

turn on

Heating

Cooling

Deadband

db 2

(non-adj. 2 ) (adj. 1-6 )

db 1

Deadband

db 2

(non-adj. 2 )

(adj. 1-6 )

HEAT/COOL DIFFERENTIAL - The Heat and Cool setpoints will not be 
    allowed to come any closer to each other than the minimum difference
    on page 15.  This minimum difference is enforced during Auto-changeover 
    operation.

    

Note:

  To increase the spread between the heating and cooling set-

    points, press the MODE button until only the heat setpoint is displayed; 
    adjust to the desired setpoint.  Press the MODE button until only the 
    cool setpoint is displayed; adjust to the desired setpoint.  Press the 
    MODE button again to enter the Auto-changeover mode where both the 
    heat and cool setpoints are displayed.

         
        

S1-THEM22P7S

Содержание S1-THEM22P7S

Страница 1: ...el COMMERCIAL S1 THEM22P7S Digital Thermostat Digital Thermostat Heat Cool HeatPump 7 DayProgrammable Heat Cool HeatPump 7 DayProgrammable Stages 2 Heat 2 Cool BacklitDigitalDisplay AuxHeatIndicator SystemPowered FahrenheitorCelsius Auto Changeover ofPowerFailure ClockBackupintheEvent KeypadLockout Upto4HourOverride ...

Страница 2: ...anced Setup Overview Daily Programming Copying the Program Normal Operation Manual Operation Page Warranty Safety Warnings Location of Controls Display Programmed Operation Clock Set Advanced Features Factory Defaults Calibration Overriding the Program S1 THEM22P7S ...

Страница 3: ...W THERMOSTAT WARNING Page 3 Safety Warnings OWNER S MANUAL This device complies with Part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation P N S1 THEM22P7S S1 THEM22P7S ...

Страница 4: ...M NEXT MODE OFF COOL HEAT AUTO i2 00PM Tu 78 COOL occupied1 Location of Controls Page 4 COOLER WARMER BUTTONS PROGRAM BUTTON Program OFF RUN program SET program OVERRIDE BUTTON NEXT BUTTON MODE BUTTON OWNER S MANUAL S1 THEM22P7S ...

Страница 5: ... Heat indicator will flash COOL Indicates the cooling mode When cooling is is energized the Cool indicator will flash HEAT COOL Indicates the system will auto matically changeover between heat and cool modes as the temperature varies AUX Indicates the 2nd stage of heat is energized When 2nd stage heat is energized the Aux indicator will flash Time period indicators These indicate the part of the p...

Страница 6: ...imes Indicates the fan will run continuously Current room temperature Indicates the program is currently being overriden for up to four hours see page 14 88 i8 88AM PM MTuWThF SaSu Start Stop Over Ride FAN 88 88 HEAT AUX COOL Unoccupied123 ON Auto Indicates the keypad is locked S1 THEM22P7S ...

Страница 7: ...DE BUTTON OWNER S MANUAL Manual Operation Program set to OFF Select Heat Cool or Heat Cool with the MODE button Normally leave the fan programmed for Auto see page 15 In Fan Auto the fan will turn on only with a heat or cool demand When Fan On is selected the fan will run continuously Adjust the desired set temperature with the COOLER and WARMER buttons NEXT BUTTON MODE BUTTON S1 THEM22P7S ...

Страница 8: ...OGRAM button Occupied 1 2 3 or Unoccupied will appear on the display Normally leave the fan switched to Auto see page 15 When Fan On is selected the fan will run continuously The desired set temperature may be temporarily overridden The thermostat will revert to the programmed settings in the following time period COOLER WARMER BUTTONS PROGRAM BUTTON OVERRIDE BUTTON NEXT BUTTON MODE BUTTON Program...

Страница 9: ...up screens Press NEXT to advance OWNER S MANUAL To slew the time more rapidly push and hold the COOLER or WARMER buttons This thermostat is preprogrammed from the factory to operate 1 or 2 Stage equipment without the need for further programming To optimize the installation of this thermostat follow the instructions in the Advanced Setup section 6 00AM Su NEXT 6 00AM S1 THEM22P7S ...

Страница 10: ...the time period programming screens will flash and can be modified with the COOLER WARMER buttons Continue the steps above until programming is complete Press the PROGRAM button twice to exit the programming screens and operate the thermostat according to the time period programming Then press the MODE button to run the program in the Heat Cool or Heat Cool mode Press the PROGRAM button once to ex...

Страница 11: ...ns page 9 Use these buttons to adjust the cool setpoint for Occ upied 1 Press NEXT to advance Use these buttons to select the maximum of occupied periods to be used on any one day Typically most installations use only Occ upied 1 OFF RUN SET PROGRAM NEXT NEXT NEXT NEXT occupied1 74 COOL occupied1 74 72 HEAT COOL occupied1 85 COOL Unoccupied Use these buttons to adjust the heat setpoint for Occ upi...

Страница 12: ...d1 6 00PM M Stop occupied1 M occupied1 Use these buttons to adjust the cool setpoint for Unocc upied Use these buttons to s the day you would like to program for the Occupied 1 time period elect Use these buttons to adjust the start time for the Occ upied 1 time period Use these buttons to adjust the stop time for the Occ upied 1 time period Use these buttons to select Occupied 1 to run on this da...

Страница 13: ... 3 programming steps are skipped Heat Cool setpoints for Occupied 1 are the same for every day of the week If desired Heat Cool setpoints for Occupied 2 3 can be adjusted differently for each day of the week If the start time is set later in the day than the stop time the program will run from the start time to midnight and from midnight to the stop time on the same day For example 9pm start 8am s...

Страница 14: ...l temporarily force the thermostat into Occupied 1 comfort settings for 30 minutes The remaining Override time will alternate with the clock The Override timer can be set up to a maximum of four 4 00 hours in increments of 30 minutes If the timer has been set for the maximum time the next press of the OVERRIDE button will reset the timer returning the thermostat to the correct time period program ...

Страница 15: ...ess Use these buttons to adjust the deadband from 1 to 6 degrees page 17 Press the PROGRAM button to enter the Advanced Setup When the clock is flashing press the NEXT button for 5 seconds Do not release the button until this screen appears NEXT NEXT NEXT NEXT 2HEAT COOL Use these buttons to select fan operation On for continuous operation Auto for heating or cooling operation only Use these butto...

Страница 16: ... Gas Electric or Heat Pump operation page 18 NEXT NEXT 0 Press NEXT to advance Use these buttons to select thermostat operation in degrees F or C Press NEXT to advance NEXT NEXT Use these buttons to adjust the Cycles Per Hour from 2 to 6 d no limit zoning d1 d no compressor lockout page 17 Press NEXT to advance 6 NEXT The following three setup steps are Read Only and may only be set with the jumpe...

Страница 17: ...when A The temperature spread from the setpoint is equal to or greater than the setpoint plus the 1st stage deadband page 14 This 1st stage dead band is adjustable from 1 6 degrees and the default is two degrees Heat Setpoint Cool Setpoint Deadband Deadband db 1 1st Stage turn on 2nd Stage turn on 1st Stage turn on 2nd Stage turn on Heating Cooling Deadband db 2 non adj 2 adj 1 6 db 1 Deadband db ...

Страница 18: ...isappear from the display then release the buttons i2 00PM M 76 68 HEAT COOL OVERRIDE ELECTRIC HEAT Selecting Electric Heat thermostat to turn on the fan immediately any time there is a heat demand Since most gas furnaces control the fan this feature should be off unless it is necessary for the thermostat to energize the fan with first stage heat page 16 will cause the ENERGY SAVING SMART FAN This...

Страница 19: ...il this screen appears After restoring factory defaults the thermo stat screen will display all icons Press the PROGRAM button to return to normal operation NEXT OFF RUN SET PROGRAM 6 88 i8 88AM PM MTuWThF SaSu Start Stop Over Ride FAN 88 88 HEAT AUX COOL Unoccupied123 ON Auto 88 i8 88AM PM MTuWThF SaSu Start Stop Over Ride FAN 88 88 HEAT AUX COOL Unoccupied123 ON Auto S1 THEM22P7S FAN Auto Press ...

Страница 20: ...ure reading using the WARMER and COOLER buttons then press the NEXT button to store the new value Press NEXT to store the new value When the Cycles Per Hour is flashing press and hold the NEXT button until this screen appears 78 NEXT NEXT 88 i8 88AM PM MTuWThF SaSu Start Stop Over Ride FAN 88 88 HEAT AUX COOL Unoccupied123 ON Auto S1 THEM22P7S Press NEXT four times until this screen appears NEXT 6...

Страница 21: ...RSON WHATSOEVER ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owner s manual including filter cle...

Страница 22: ... D A Y Copy Mon Tue M O N D A Y T U E S D A Y DAY PERIOD HEAT START TIME COOL Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Programming Wo...

Отзывы: