Installer Setup  -  

Timers and Deadbands

Deadband Settings 

(setup steps 28 - 37)

The Deadband is the number of degrees or minutes that the thermostat waits 

before it initiates the stages of heating or cooling.
1st Stage Deadband 
(setup step 28) - Specifies the minimum temperature 

difference between the room temperature and the desired setpoint before 

the first stage of heating or cooling is allowed to turn on. (1 - 6 degrees) For 

example, if the heat setpoint is 68˚ and the 1st Stage deadband is set to 2 

degrees, the room temperature will need to reach 66˚ before the heat turns on.
2nd Stage Deadband (setup step 29) - Specifies the additional minimum 

temperature difference after the first stage turns on before the second stage is 

activated. (0˚ - 10˚)
3rd Stage Deadband (setup step 30) - Specifies the additional minimum 

temperature difference after the second stage turns on before the third stage is 

activated. (0˚ - 10˚)
4th Stage Deadband (setup step 31) - (Two Stage heat pump only) - Specifies 

the additional minimum temperature difference after the third stage turns on 

before the final stage of strip heat is activated. (0˚ - 10˚)
Minutes Between 1st and 2nd Stage (setup step 32) - Specifies the minimum 

time (in minutes) after the first stage turns on before the second stage can turn 

on. (0 - 60)
Minutes Between 2nd and 3rd Stage (setup step 33) - Specifies the minimum 

time (in minutes) after the second stage turns on before the third stage can 

turn on. (0 - 60)
Minutes Between 3rd and 4th Stage (setup step 34) - Specifies the minimum 

time (in minutes) after the third stage turns on before the final stage can turn 

on. (0 - 60)
Second Stage Turnoff Point (setup step 35) - Specifies whether second stage 

will turn off at first stage deadband or remain on until the room temperature 

demand is satisfied. Choose between Deadband or Setpoint.
Third Stage Turnoff Point (Setup Step 36) - Specifies whether third stage will 

turn off at second stage deadband or remain on until the room temperature 

demand is satisfied. Choose between Deadband or Setpoint.
Fourth Stage Turnoff Point (Setup Step 37) - Specifies whether fourth stage 

will turn off at third stage deadband or remain on until the room temperature 

demand is satisfied. Choose between Deadband or Setpoint.

Содержание S1-TBSU305-S

Страница 1: ...Owner s Manual Installation Instructions Optional accessories available including Wi Fi Programmable Digital Thermostat Commercial model S1 TBSU305 S...

Страница 2: ...odically firmware updates are released by the manufacturer to add features and or performance enhancements This manual was produced reflecting the most current firmware feature set at the time of publ...

Страница 3: ...ard to deadband Icon The word or symbol that appears on the thermostat display Mode The current operating condition of the thermostat i e Off Heat Cool or Auto Non Programmable Thermostat A thermostat...

Страница 4: ...s 18 Holiday 19 Emergency Heat 19 Wireless Module 20 Service Filter 22 Runtimes 23 Time Period Programming 24 INSTALLER SETUP Setpoint Limits 26 Timers and Deadbands 27 Programming Fan Operation 28 Mi...

Страница 5: ...Know Your Thermostat Optional WiFi Module Backlit Scrolling Display Backlit LCD Display Heat or Cool Demand Indicator Red Heat Green Cool Backlit Cooler Warmer Buttons Setup Buttons Behind Door Overri...

Страница 6: ...2 Get To Know Your Thermostat Setup Buttons...

Страница 7: ...m temperature and displays the outdoor temperature when selected 5 Mode Indicators Selects the operational mode of the equipment HEAT Indicates the heating mode COOL Indicates the air conditioning mod...

Страница 8: ...ode 10 Desired SetTemperature Indicates desired room temperature s Also displays the highest and lowest temperatures for the day 11 Wi Fi icons One dot indicates the thermostat recognizes the wireless...

Страница 9: ...Indicates 2nd stage electric strip heat is being used when the thermostat is programmed for Heat Pump operation Only the Aux icon will appear during Cool to Dehumidify to indicate Reheat operation 16...

Страница 10: ...buttons Press the SET CLOCK button to confirm settings NOTE To adjust the time by hours press and hold the FAN button while pressing the WARMER or COOLER buttons Selecting the Heat or Cool Mode Selec...

Страница 11: ...mode when running the program and the thermostat shows unoccupied Using the Override Button Unoccupied Operation During programmed unoccupied periods pressing the OVERRIDE button will force the therm...

Страница 12: ...ing outdoor button will show the temperatures for your location if you don t have a wired sensor connected Note If no outdoor sensor is connected and there isn t outdoor temperature via Wi Fi then 2 d...

Страница 13: ...he power to the Heating Air Conditioning system at the main fuse panel Most residential systems have a separate breaker for disconnecting power to the furnace Remove the cover of the old thermostat If...

Страница 14: ...t follow Wire from the Install on the old thermostat Function new thermostat terminal marked connector marked G or F Fan G Y1 Y Cooling Y1 W1 W Heating W1 0 B Rh R M Vr A Power R C Common C O B Rev Va...

Страница 15: ...R connections REMOTE Remote sensor SENSOR connections DRY Dry Contact CONTACT connections IMPORTANT This thermostat requires both R 24 VAC Return and C 24 VAC Common be connected to the backplate term...

Страница 16: ...sen the thermostat will energize the fan in heating 2 When GAS EL or HP is set for HP This switch GAS or ELEC defines the Aux Heat type When GAS is chosen the auxiliary heat will not be allowed to run...

Страница 17: ...ntial Commercial 1 Stage Cooling with 1 stage Electric Heat 5 Wire 1 Stage Cooling 1 Stage Heat 24VAC Power 24VAC Common 1st Stage Heat 1st Stage Cool Fan Residential Commercial 2 Stage Cooling with 3...

Страница 18: ...ges Residential Commercial Heat Pump with O Reversing Valve 6 Wire 1 Stage Cooling 2 Stage Heat R 24VAC Power C 24VAC Common W1 O B Reversing Valve Y1 1st Stage Compressor Cool or Heat W2 Aux Heat G F...

Страница 19: ...allation Instructions Sample Wiring Diagrams Dry Contact R G W1 O B W2 Y1 Y2 W3 DEHUM HUM C AUX REMOTE SENSOR OUTDOOR SENSOR DRY CONTACT 12 11 10 9 8 7 6 5 4 3 2 1 Accessory such as Time clock or door...

Страница 20: ...Press WARMER forYes or COOLER for No IfYes is chosen press WARMER to turn on heat or COOLER to turn on Cooling The scrolling display will read NOTHING ON Next Press WARMER to turn on and cycle up thro...

Страница 21: ...and seven levels of brightness Night Dimmer setup step 5 Selecting On allows for automatic dimming of the display at night Night Dimmer Brightness setup step 6 The nighttime backlight can be adjusted...

Страница 22: ...w Words Centered Fast 12 00 12 00 WARMER COOLER MODE SETUP DISPLAY 1 Am Outdoor COOL SET HEAT SET 78 74 68 85 A Am Outdoor COOL SET HEAT SET 78 74 68 85 B Example of Whole Words Centered Each press of...

Страница 23: ...onfirm your setting press the HOLIDAY button again When the thermostat is programmed for Holiday operation and the thermostat is in the Program On mode running an Occupied Unoccupied time period sched...

Страница 24: ...many of the wireless devices this status includes Battery Level Signal Strength and LastTime Updated If there is an optional wireless module installed the ACCESSORY SETUP button allows the user to li...

Страница 25: ...s screens listed below a Wi Fi status connecting connected etc b Signal strength c Access point name d IP address e MAC address f Skyport status connecting connected with etc g Local API status Enable...

Страница 26: ...rs of fan runtime in the Heating mode Cooling mode and in stand alone Fan operation Press FAN to reset Current Service Filter Calendar Days Setup Step 10 This counter displays the total number of cale...

Страница 27: ...V Lamp Runtime setup steps 12 15 Current UV Lamp Calendar Days setup step 12 This counter displays the total number of calendar days that have elapsed since last reset to help the user track UV lamp r...

Страница 28: ...nly and OFF Heat and Cool Allows the thermostat to turn on heating or cooling depending on which one has been manually selected Auto Changeover is not available when this mode is selected Heat Only Al...

Страница 29: ...he mode for the occupied period The choices are Off Heat only Cool only and AUTO changeover Adjust the Occupied Cool Setpoint Press the Warmer or Cooler buttons to adjust the Cooling setpoint for comf...

Страница 30: ...our your HVAC unit may energize For example at a setting of 6 cycles per hour the HVAC unit will only be allowed to energize once every 10 minutes The Cycles Per Hour limit may be overridden and reset...

Страница 31: ...ature difference after the third stage turns on before the final stage of strip heat is activated 0 10 Minutes Between 1st and 2nd Stage setup step 32 Specifies the minimum time in minutes after the f...

Страница 32: ...120 seconds If set to 0 the fan will not run after a call for cooling or electric strip heating has been satisfied Comfort Recovery setup step 41 With Comfort Recovery on the thermostat will attempt...

Страница 33: ...ll blink This setting is useful for allowing a twist timer to force occupied settings FDD If FDD is selected when the dry contact is active EQUIPMENT FAULT will appear on the display HOLIDAY If HOLIDA...

Страница 34: ...ttings of the thermostat in order to reduce energy usage on demand This is known as Automated Demand Response or ADR for short You must register to participate in a utility sponsored program if offere...

Страница 35: ...to respond to the energy provider s signals It also sets operational parameters for the thermostat The left column of the ADR configuration page allows or prevents access by the utility Here communica...

Страница 36: ...Selecting the Overview tab of the ADR page will cause a summary of ADR events to be displayed Installer Setup Automated Demand Response 32...

Страница 37: ...atic Setpoints will set the heat and cool setpoints to the values specified in setup steps 50 and 51 Event Max Cool Setpoint setup step 48 Event Min Heat Setpoint setup step 49 Specifies the range of...

Страница 38: ...setpoint can be automatically raised by 1 to 10 degrees DISPLAY INDICATIONS WHEN AN ADR EVENT IS HAPPENING After setting your desired values for use during an ADR event the scrolling display will give...

Страница 39: ...utton press the WARMER and COOLER buttons together The icon will appear on the display then release the buttons Press all three buttons in the order outlined above for keypad lockout To unlock the key...

Страница 40: ...anently lost 1 Press and hold SETUP for 10 seconds All icons will appear on the display Keep pressing the SETUP button until you see this screen 2 After all the icons appear release SETUP Press and ho...

Страница 41: ...urposes and is intended for use by a qualified technician Technician Setup contains the following options View the version number of the thermostat View the Dip Switch equipment type settings View the...

Страница 42: ...0 720 Days 0 15 Set UV Lamp Calendar Days 23 0 720 Days 0 16 Language 17 English Espanol Francais English 17 Scrolling Method 18 L R Slow L R Fast Word L R Whole Slow Word L R Fast Words Whole Word L...

Страница 43: ...Fahrenheit F Celsius C F 41 Comfort Recovery 28 On Off Off 42 Dry Contact Polarity 29 Open Closed Open 43 Dry Contact Use 29 Condensate Pan Occupied FDD Holiday 44 Skyport 29 On Off On 45 Local API 29...

Страница 44: ...point Limits page 26 SYMPTOM The heating does not attempt to turn on CAUSE The heating setpoint is set too low REMEDY Raise the heating setpoint or raise the heating set point limit See Setpoint Limit...

Страница 45: ...WHATSOEVER ALL WORK UNDERTHETERMS OFTHIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME ASTHEIR WARRANTY PERIOD ONLYTHE REMAININGTIM...

Страница 46: ...ture Adjustment Range Accuracy 10 RH from 30 70 RH 50 90 F Humidity Wire Size Deadband Operating Storage Ambient Conditions Compliance Dimensions Shipping Weight This equipment has been tested and fou...

Страница 47: ...P N 88 1259 rev 2 06 19 Patent Pending...

Отзывы: