39
Advanced Setup Table
Df = Factory Default Setting
Step# Description
Pg# Range
Df
31
Control to Temp Source
28
Thermostat, Wired Remote*,
Thermostat
Wireless Remote, Average of
Wireless Remotes, Average
Thermostat and Wired Remote*,
Average All Sensors. *Option
only if prior step = “Remote”
32
Wireless Remote to Use
28
list of wifi sensors currently
first linked
linked to thermostat.
sensor in list
*This step only appears if prior
step = “Wireless Remote”
33
Humidity Only With Heat
25 On, Off
Off
34
Fan With Humidity Demand
25 Fan On, Fan Off
Fan Off
35
Fan With Dehumidify Demand
25 Fan On, Fan Off
Fan Off
36
Cool To Dehumidify
25 On, Off
Off
37
Maximum Occ Dehum Overcool
26 0 - 5 Degrees
2
38
Maximum Unocc Dehum Overcool
26 0 - 20 Degrees
2
39
Reheat Operation W/Cool To Dehum. 26 On, Off
Off
40
Fan Off Delay
25 0 - 120 Seconds
0
41
F/C
28 Fahrenheit (F), Celsius (C) F
42
Dry Contact Polarity
27 Open, Closed
Open
43
Dry Contact Use
27
Condensate Pan, Unoccupied, FDD
44
Unoccupied Mode
27 Heat,Cool,Auto,Off
Off
45
Unoccupied Cool Setpoint
27 35 - 99 Degrees
85
46
Unoccupied Heat Setpoint
27 35 - 99 Degrees
55
47
Humidity Polarity
26 Open, Closed
Open
48
Dehumidify Polarity
26 Open, Closed
Open
49
Dehumidify only with Cooling
26 On, Off
On
50
Skyport
32 On, Off
On
51
Local API
32 On, Off
Off
52
ADR
32 On, Off
Off
53
ADR Action
32
Observe Setpoint Offset,
Observe
Observe Static Setpoints
Setpoint Offsets
54
Event Max Cool Setpoint
32 35 - 99
85
55
Event Min Heat Setpoint
32 35 - 99
65
56
Static Cool Setpoint
33 35 - 99
78
57
Static Heat Setpoint
33 35 - 99
68
58
Cool Setpoint Offset
33 1 to 15
4
59
Heat Setpoint Offset
33 -1 to -15
-4
60
Press Fan To Clear All Messages
28
Содержание S1-TBSU304-S
Страница 2: ......
Страница 7: ...Setup Buttons 2 Get To Know Your Thermostat...