background image

 

5

   (2000V

rms

 + 500V DC 

<

 4000 V

rms

).  

 
- High energy may be stored in the output capacitors. Don’t cause a short circuit across the output. 
 
- Don’t remove wires from the output terminals under load condition, especially at the higher voltage. 

There probably will occur an arc, which may damage the unit. First turn off a load by disable 
OUTPUT switch. 

 
- The time between turning mains switch off and on must be min. 60s. 
 
- The same type should replace fuses. 
 
- Output voltage indicated on the display after turning disable OUTPUT switch off is present until 

output capacitors discharge (depends on the load). 

 
- To avoid overheating the output capacitors by a pulsating load, the AC component of the load 

current should be limited. One method of decreasing the AC current on the output capacitor is by 
using a large external electrolytic capacitor in parallel with load. This also reduces problems of the 
inductance in a long lead. Care must be taken so that the capacitor in combination with the load 
inductance will not form a serial resonant circuit. 

 
- The output voltage is available 2s after mains switch on. This feature may be improved according to 

customer requirements.  

 
- Serial operation is allowed up to 300V total voltage. The power supplies can be connected in series 

without special precautions. 

 
- Parallel operation of the two units without active current sharing is allowed. It is recommended to 

connect a diode per each unit – anode to plus terminal, cathode to common load and to set the same 
voltage on both units at the turning disable OUTPUT switch off. When the both output voltages are 
not the same nothing terrible happen because each unit has a current limitation. In parallel operation 
may occur a   higher ripple voltage which my be up to 2 times of the normal ripple voltage value. In 
case of short circuit at any of the outputs of paralleling units, both units result short – circuited. 

 
- Reverse polarity protection can be achieved with an external fuse combined with a rapid diode as in       

following figure 3: 
 

This case may occur especially in the battery charger application. After applying reverse polarity     

SPS1000

+

-

+

incorrect polarity

of the battery

Fig.3

Содержание SPS1000 SERIES

Страница 1: ...t is limited approximately to 60A 10ms This must be taken into account at a fusing of the line outlet It is recommended to use 16A normal fuse or 10A slow one The rectified 230V AC 300V DC is chopped...

Страница 2: ...nit Voltage is indicated on the 3 digit display and the current at the same time on the 3 digit display Power supply output may be turned on or off by the Disable OUTPUT switch at any time independent...

Страница 3: ...PE 50Hz 230V 10 TN S Protection achieved by basic insulation and connection to earth for all conductive parts that are capable of assuming hazardous voltage if the basic isolation fails An output sec...

Страница 4: ...ondition MAINTENANCE Power Supply SPS 1000 normally needs no maintenance or calibration Only care must be taken not to obstruct cooling of the unit When a unit is equipped by a dust filter which must...

Страница 5: ...oad inductance will not form a serial resonant circuit The output voltage is available 2s after mains switch on This feature may be improved according to customer requirements Serial operation is allo...

Страница 6: ...TTL logic and lower one could be able to trigger the thyristor crowbar under normal operating condition due to a disturb noise Avoid condensation inside the power supply break down could be the resul...

Страница 7: ...after this string send character 0x0D ENTER Meaning of each symbol S beginning of message Z power supply switched ON V power supply switched OFF Tu switch OFF power supply resp his output zero voltage...

Отзывы: