2.5

   Discharge current

 

The battery discharge current cannot exceed the maximum discharge current specified in the specification. Excessive current 
discharge will cause the battery to heat up and reduce its capacity.

 

 

2.6 

  Over-discharge

 

The  battery  may  be  permanently  damaged  when  the  battery  voltage  is  less  than  6V,  and  the  product  quality  assurance  of 
Soshine will be invalid. According to 11.1.3.2 this specification, the internal energy consumption of the system should be reduced 
to  minimum  when  the  discharge  cut-off  voltage  is  below  10.8V,  and  the  storage  time  is  prolonged  before  recharging.  The 
customer needs to train the user to recharge the battery in the shortest time to prevent the battery from over-discharge state.

 

 

2.7 

  Battery storage

 

If the battery is expected to be stored for more than 30 days, the SOC should be adjusted to about 30%. If the battery is expected 
to be stored for more than 180days, the SOC should be adjusted to about 80% and the battery to be charged and discharged at 
least once in the whole SOC range ( 10.8~14.2V) for every 90 days .

 

 

2.8

   Charge at low temperatures

 

The battery should avoid charging (including standard charging, quick charging, emergency charging) in the low-temperature 

conditions which is prohibited in this specification, otherwise, unexpected capacity reduction may occur. The battery 

management system should be controlled according to the minimum charge and regenerative charging temperature. It is 

forbidden to charge when temperature is lower than the temperature conditions specified in this specification. Otherwise, Soshine 

shall not be liable for quality assurance

 

 

2.9

   Battery heat diffusion

 

In the design of the electric box, the heat diffusion of the battery should be fully considered. Soshine shall not be responsible for 
the quality assurance due to the overheating of the battery or battery caused by the design of the electric box.

 

 

2.10

   Waterproof and dustproof

 

The waterproof and dustproof problem should be fully considered in the electrical box design, and the electric box must meet the 
waterproof and dust-proof grade stipulated by the relevant national standards. Soshine is not responsible for quality assurance 
due to the damage caused by the waterproof and dustproof problem (such as corrosion, rust, etc.).

 

 

3

 

Charger Requirements 

 

3.1

   Special charger for LiFePO4 battery

 

It is recommended to use a special charger for LiFePO4, constant current and constant voltage charging (fully charged cut-off 
voltage 14.2V), with short circuit protection, overcharge protection, reverse connection protection, and anti-backfill function. 

 

Charging current 12A (max).

 

3.2

   Solar panel intelligent charge and discharge controller

 

Select LiFePO4 charger mode.

 

Constant current and constant voltage charging (fully charged cut-off voltage 14.2V), with short circuit protection, overcharge 
protection, reverse connection protection, and anti-backfill function. 

 

Charging current 12A (max)

 

3.3 

  Lead-acid battery charger

 

It is recommended to use three-stage charger with overcharge protection, and short-circuit protection.

 

Voltage range: charge cut-off voltage 13.5~4.6V, float voltage 13.7~3.8V, over discharge voltage 10.8~11V.

 

Charging current 12A (max)

 

Lead-acid chargers that meet the above requirements can be used, but the battery may be overcharged, and the long-term use 

will shorten the life of some batteries or not fully charged, and the full capacity will be reduced by about 5% compared to the 

normal capacity.

 

 

 

Содержание 12.8V24AH

Страница 1: ...DOC IFR12 8V24AH 4S4P M5 Page 1 Of 9 Pages LiFePO4 Battery 12 8V24AH Instruction Manual Soshine International www soshine com cn summer soshine com cn...

Страница 2: ...01C 240mA 2 3 4 Short circuit Protection Disconnect When a short circuit occurs the battery is disconnected from the over current 2 3 5 Over current Protection According to 4 11 and 4 14 the battery...

Страница 3: ...quality assurance 2 9 Battery heat diffusion In the design of the electric box the heat diffusion of the battery should be fully considered Soshine shall not be responsible for the quality assurance...

Страница 4: ...5C 12A For continuous discharge mode Ambient temperature 25 C 4 14 Discharge Current 2C Maximum 24A The surface temperature of the cells 60 C 4 15 Impedance Battery Internal 60m Internal resistance me...

Страница 5: ...rotection Overcharge protection delay 0 5S 2S 5 8 Protective voltage 2 0 0 1V 5 9 Restore voltage 2 70 0 1V 5 10 Over discharge protection delay 10 200mS 5 11 Over discharge protection Over current pr...

Страница 6: ...s essentially flat meaning that a 20 charged battery will be providing nearly the same output voltage as an 80 charged battery This prevents any issues caused by the voltage sag common to lead acid as...

Страница 7: ...FR12 8V24AH 4S4P M5 Page 7 Of 9 Pages 8 Battery Initial Dimensions and Label 8 1 Dimensions 8 2 Battery label No Item Unit mm 1 Battery length L 181 0 2 2 Battery width W 167 0 2 3 Battery height H 77...

Страница 8: ...hould stop using the battery Any violation of the requirements shall be exempted from Soshine s quality guarantee responsibility which based on product sales contract and this specification 11 Storage...

Страница 9: ...s specification shall be agreed by both parties 16 CAUTIONS IN USE To ensure proper use of the battery please read the manual carefully before using it Handling When charging and discharging do not re...

Отзывы: