Technical Overview 

Links

 

The  CL-CO-RFG65x  is  a  series  of  gas leak alarm systems, 
that are designed for the detection of gas leaks in spaces 
such as boiler plant rooms, workshops and other industrial 
gas installations, to provide safety alarm and shutdown 
facilities on detection of gas leakage. 1, 2 or 3 channel ver-
sions are available. 
 

Installation 

 
1.  The GL-CO-RFG65x should only be installed by a compe-

tent, suitably trained technician, experienced in installa-
tion with hazardous voltages. (>50Vac & <1000Vac or 
>75Vdc & 1500Vdc)  

 

 

 

 

 

2.  Ensure that all power is disconnected before carrying out 

any work on the GL-CO-RFG365x.   

 

 

 

3.  Maximum cable is 2.5mm², care must be taken not to 

over tighten terminals. 

 

 

 

 

 

4.  Separate the base from the cover.   

 

 

 

 

5.  If DIN rail mounting clip onto the DIN rail.   

 

 

 

6.  Make connections as required (see page 4 & 5 for     

examples) and links as appropriate (see below). NB It is 
advised that no more than 2 cables be inserted into a 
single terminal. Use external junction boxes if necessary.
 

 

 

 

 

 

 

 

7.  Replace the cover on the base using the 4 screws pro-

vided, if panel mounting fix to panel door, using the 
panel mounting kit. 

 

Panel Mount Cut-Out 

 

Panel cutout: 138 x 138 ±0.5% 

 
 
 
 
 

Link Functions: 
 
M - F1  

 

No link = Internal buzzer enabled 
Linked = Internal buzzer disabled 
 
F2 - F3  

 

No link = Relay normally energised when no gas present 
Linked = Relay normally de-energised when no gas present 
 
F3 - F4  

 

No link = Relay with latching alarm 
Linked = Relay with non-latching alarm  
 
B2 - H2 
Linked = B2 sensor not connected 
 
B3 - H3  
Linked = B3 sensor not connected 
 
Operational Relay Output: 
 

 

 

 

 

 

              

When in alarm:  
F2 - F3 linked   

1 - 3 closes, 2 - 3 opens                  

F2 - F3 unlinked 

1 - 3 opens, 2 - 3 closes 

 
Latching alarm and Reset: 
 
F3 - F4 linked: 
Alarm ceases when the gas concentration falls below the 
threshold level and the ALARM LED blinks slowly. Press the 
RESET button to clear the LED status. 
 
F3 - F4 unlinked: 
Alarm continues even when the gas concentration falls be-
low the threshold level. To deactivate press the RESET but-
ton for at least 5 seconds.

 

 

 

Alarm Levels 

 
Alarm thresholds 
Natural gas alarm threshold: 

 

 

 

 

0.5% to 1.25%  

(0.8% with sensitivity =0)

 

(5000 to 12,500ppm) 

LPG alarm threshold:   

 

 

 

 

0.22% to 0.56% 

(0.35% with sensitivity =0)

 

(2200 to 5600ppm) 

CO alarm threshold: 

 

 

 

 

 

0.02% to 0.5%  

(0.03% with sensitivity =0)

 

(200 to 500ppm) 

Содержание GL-CO-RFG65 Series

Страница 1: ...2g DIN 40046 Relay outputs 2 x SPDT 250V 5 1 A Housing dimensions 105 x 115 x 70mm Housing materials Cover ABS Base Nylon Housing protection IP40 Panel mount housing dim 142 x 142 x 125mm Sensor dimensions 77 x 77 x 44 Sensor material Nylon Sensor protection IP44 Ambient Storage temp 25 to 60 C Operating temp 0 to 45 C RH Class F Din 40040 Country of origin Italy GL CO RFG651 1 Channel gas leak al...

Страница 2: ...le terminal Use external junction boxes if necessary 7 Replace the cover on the base using the 4 screws pro vided if panel mounting fix to panel door using the panel mounting kit Panel Mount Cut Out Panel cutout 138 x 138 0 5 Link Functions M F1 No link Internal buzzer enabled Linked Internal buzzer disabled F2 F3 No link Relay normally energised when no gas present Linked Relay normally de energi...

Страница 3: ...5 to 2 minutes with the FAULT and ALARM LEDs flashing to allow the sensor to stabilise When the gas concentration exceeds the pre alarm thresh old the ALARM LED blinks When the gas concentration exceeds the alarm threshold after a delay of about 20 seconds The internal buzzer will sound if enabled The ALARM LED switches ON Activates the operational control Self diagnostics In the event of a fault ...

Страница 4: ...861225 GL CO RFG65x Issue 5 4 Date Of Issue 28 10 2008 2008 Sontay Limited All rights reserved Front Panels Example Connections 1 Sensitivity potentiometer 2 Power supply LED 3 Fault LED 4 Alarm LED 5 Reset button Dimensions Basic operation GL CO RFG652 230Vac Supply ...

Страница 5: ...terest of technical improvement this specification may be altered without notice Page 5 of 5 UK Sales Tel 0845 345 7253 International Tel 44 1732 861225 For the latest information and product updates register at www sontay com GL CO RFG65x Issue 5 4 Date Of Issue 28 10 2008 2008 Sontay Limited All rights reserved Example Connections continued GL CO RFG653 230Vac Supply GL CO RFG653 12V Supply ...

Отзывы: