Commissioning of the photovoltaic power plant 

Before initiation of the generator, please check all components (observe the installation instructions of other 
components), the electrical connection and all plugs, that they are connected correctly and ensure that the 
connection is tight.

 

 

Solar generators with a direct current voltage from more than 50V must be installed/initiated 
by qualified persons!

 

The open circuit voltage of every serial connection should be checked after initiation. Follow the rule: Result 
of the measurement = sum of the open circuit voltages of the single modules. Consider the actual time, sun 
irradiation, shadowing and other factors while measuring the open circuit voltage, otherwise the result of the 
sum and the single results could deviate considerably. 

Maintenance 

  Soiling on the module surface can lead to a reduction in performance. 

  Clean the modules as required and soiled with plenty of water and a soft cloth or sponge without 

any detergent. Do not use high pressure cleaners! 

  If other additives or devices like aggressive chemicals, scrubbing agents, sharp blades or steel 

wool are used the guarantee and product warranty will be invalid! Never wipe off or scrape off 
pollution in a dry state of the module surface. 

  An additional application of water / dirt resistant coatings can affect the efficiency of the modules 

and also the yield, in a negative way. 

  Check the module wiring and the single module plugs to ensure they are clean, corrosion free, 

mechanically ok and tight in regular intervals. 

ATTENTION: Never disconnect the plugs under load!

 

  Free the modules, if necessary, from high snow loads. 

  Check the substructure in regular intervals for their tightness. 

  Never try to open or repair parts of the module or of the junction box on your own. 

  All other trouble shootings, repairing and maintenance works must be done by qualified, skilled 

staff/persons. 

 

 

 

 

 

For further information relating to warranties etc. please read through the GENERAL TERMS 
AND CONDITIONS of KIOTO Photovoltaics GmbH. 

 

Содержание KIOTO SOLAR Glas-60 framed Series

Страница 1: ...PHOTOVOLTAIC MODULES Installation manual Power 60 Standard MAXIM ALPIN Glas 60 with without frame Project 60 halfcut...

Страница 2: ...ctions for mounting 4 Electrically 4 Mechanically 5 Advices double glass modules without frame 5 Fixing points of the KIOTO modules 6 Electrical connection of the photovoltaic generator 6 Detailed inf...

Страница 3: ...or other abrasive liquids Do not handle the module at the junction box Do not pull the module connection cables by forces Do not drill any holes in the framework or other components of the module Do...

Страница 4: ...e followed stringently Remember in de energized state high contact voltage could occur and or deadly electric arc can be generated Cover the single module with a lightproof material during the mountin...

Страница 5: ...of application Ensure that there is adequate ventilation behind the modules To generate optimal output of the photovoltaic generator consider the perfect alignment and mounting angle of the photovolta...

Страница 6: ...be securely fastened with continuous support profiles at least 4 points The PV modules can only be attached to the substructure by clamping from the front The clamping area must be at least 400 mm per...

Страница 7: ...se high quality cables to assure a failure free operating Ensure good isolation and whether UV durability of the cables The rated voltage of the solar cable must be 1000V minimum If possible use flexi...

Страница 8: ...be done by qualified persons to ensure an optimized energy yield For safety reasons and to minimize maintenance works a DC disconnector should be installed between the generator and the inverter This...

Страница 9: ...n in performance Clean the modules as required and soiled with plenty of water and a soft cloth or sponge without any detergent Do not use high pressure cleaners If other additives or devices like agg...

Страница 10: ...Seite 10 von 12 KIOTO_Installation_manual_2021 KIOTO Photovoltaics GmbH Solarstra e 1 9300 Sankt Veit Glan sterreich 06 2021...

Страница 11: ...Seite 11 von 12 KIOTO_Installation_manual_2021 KIOTO Photovoltaics GmbH Solarstra e 1 9300 Sankt Veit Glan sterreich 06 2021...

Страница 12: ...KIOTO Photovoltaics GmbH Solarstra e 1 Industriepark A 9300 St Veit Glan T 43 0 4212 28 300 0 E office kioto com www kiotosolar com...

Отзывы: