background image

Publisher

sonnen GmbH

Am Riedbach 1

D-87499 Wildpoldsried

Service number

+61 13 7666

Email

[email protected]

Document

Document number

536

Part number

1000051

Version

02

Valid for

AU, NZ

Publication date

05/02/2021

9007199366748683

IMPORTANT

„ 

Read this documentation carefully before installation / operation.

„ 

Retain this document for reference purposes.

EN

Operating instructions sonnenProtect 2500

Содержание sonnenProtect 2500

Страница 1: ...Operating instructions for operators sonnenProtect 2500 for sonnenBatterie hybrid 9 53 KD 536 Part no 1000051 Version 02 info sonnen de sonnen de ...

Страница 2: ...sonnen com au Document Document number 536 Part number 1000051 Version 02 Valid for AU NZ Publication date 05 02 2021 9007199366748683 IMPORTANT Read this documentation carefully before installation operation Retain this document for reference purposes EN Operating instructions sonnenProtect 2500 ...

Страница 3: ...ge inside the sonnenProtect 6 3 Product description 7 3 1 Technical data 7 3 2 System components of the sonnenProtect 8 3 3 Type plate 8 3 4 Symbols on the outside of the sonnenProtect 9 4 Operation 10 4 1 Function 10 4 1 1 Grid operation no grid outage 10 4 1 2 Backup operation grid outage 11 4 1 3 Backup operation overload behaviour 12 4 2 Setting the backup buffer 13 5 Switching off the sonnenP...

Страница 4: ...s document Complete designation Designation in this document sonnenProtect 2500 sonnenProtect sonnenBatterie hybrid 9 53 Storage system 1 3 Explanation of symbols DANGER Extremely dangerous situation leading to certain death or serious injury if the safety information is not observed WARNING Dangerous situation leading to potential death or serious injury if the safety information is not observed ...

Страница 5: ...roduct doc umentation of the appropriate storage system The sonnenProtect must only be installed and used at suitable installation location The transport and storage conditions must be observed Especially the following uses are not permissible Operation in flammable environments or areas at risk of explosion Operation in locations at risk of flooding Operation outdoors Failure to comply with the c...

Страница 6: ...s and only when in perfect working order Safety devices must never be overridden blocked or tampered with The interfaces of the sonnenProtect and the storage system must be connected in ac cordance with the product documentation All repairs on the sonnenProtect must be performed by authorised service technicians only 2 5 Voltage inside the sonnenProtect 5 min The sonnenProtect contains live electr...

Страница 7: ...itch to emergency operation takes place automatically through the storage system Switchover time max 15 seconds Threshold power none starting from 0 W Dimension Weight Dimension H W D in mm 230 200 122 Weight in kg 4 3 Safety Protective devices Protection class I PE conductor Degree of Protection IP30 Overvoltage category III Protective functions Overcurrent protection fault current protection Res...

Страница 8: ...butor 6 Miniature circuit breaker F3 P 3 3 Type plate The type plate is located on the outer surface of the sonnenProtect The type plate can be used to uniquely identify the sonnenProtect The information on the type plate is required for the safe use of the system and for service matters The following information is specified on the type plate Item designation Item number Technical data A duplicat...

Страница 9: ...ical voltage Wait five minutes after switching off ca pacitor de energising time CE mark The product meets the requirements of the applicable EU Directives WEEE mark The product must not be disposed of in household waste dispose of it through environmentally friendly collection centres Observe the documentation The documentation contains safety in formation ...

Страница 10: ...ted to phase L1 6 Storage system 2 Consumer connected to phase L2 7 Battery of the storage system 3 Consumer connected to phase L3 8 PV system 4 Consumer connected to backup circuit 9 Public electricity grid 5 sonnenProtect In grid operation the consumers connected to phase L1 to L3 and the consumers connec ted to the backup circuit 1 4 are connected to the public electricity grid 9 All con sumers...

Страница 11: ... house 4 are thereby supplied with electrical power Consumers connected to the phase L1 L2 or or L3 1 3 will not be supplied with electrical power The switchover from grid to backup operation is signaled by the sonnen Eclipse light ring on the storage system The color of the sonnen Eclipse changes from white normal opera tion to green backup operation Electrical power generated by the PV system 8 ...

Страница 12: ...l no longer be supplied with power In this case switch off the electrical loads or reduce their power consumption and then switch on the miniature circuit breaker F3 P in the sonnenProtect Case 2 Overload detection by storage system In special overload cases the control of the storage system reacts earlier than the integ rated fuse of the sonnenProtect In this case the miniature circuit breaker in...

Страница 13: ...The sonnenProtect was set up by the installer using the commissioning assistant 2 Proceed as follows to access the storage system web interface Enter the following address into your browser s address line https find my sonnen batterie com The following window appears 12345 123 456 78 99 Click on the blue LAN IP number The login page appears Log in as user with the following password sonnenUser3552...

Страница 14: ...4 Operation 14 20 Operating instructions sonnenProtect 2500 ...

Страница 15: ...in the relevant product documentation After switching off the consumers connected to the backup circuit s can no longer be supplied with electrical energy from the battery of the storage system NOTICE Deep discharge of the battery modules Destruction of the battery modules Do not disconnect the storage system from the public electricity grid for long periods of time Never continue to operate batte...

Страница 16: ...aken Every 6 months Check the function of the RCD with help of the Test key Table 3 Checking function 6 2 Cleaning NOTICE Use of unsuitable cleaning agent and or excessive water Material damage because of scratched surfaces and or damage caused by penetration of water Do not use scouring cloths sponges or cleaning agent Use only moist cloths not wet cloths to clean the system Do not use water jets...

Страница 17: ...tion of the sonnenProtect Danger to life due to electrocution The sonnenProtect must only be uninstalled by authorised electricians 7 2 Disposal Illustration 4 WEEE symbol The sonnenProtect must not be disposed of as do mestic waste Dispose of the sonnenProtect in an environ mentally friendly way through suitable collec tion systems ...

Страница 18: ... charge state and therefore damage the batteries If the PV system generates electrical power the backup operation will continue as soon as excess power is available If the PV system does not generate elec trical power the only thing to do is wait until the grid outage passes and the public electrical grid once again starts supplying electrical energy Then the sonnenProtect automatically switches t...

Страница 19: ...er consumption does not exceed the nominal power or when switching on the maximum power of the sonnenProtect Then switch on the miniature circuit breaker F3 P again The storage system automatically restarts the backup opera tion Backup operation stops The RCD F4 P in the sonnenProtect has switched off The eclipse of the storage system is green The RCD has detected fault currents in the backup circ...

Страница 20: ...sonnen GmbH Am Riedbach 1 D 87499 Wildpoldsried ...

Отзывы: