► Connect all modules separately and 
restart system and to if it is working 
correctly to help identify faulty module 
 
► Connect working modules and restart 
system ensuring that all modules in the 
system are in a range of 1V.  

System logs out when in the 
Commissioning Assistant  
 

Normally due to automatic 
firmware updates 

► Wait for 20 minutes and repeat the 
commissioning procedure as the firmware 
update will have taken affect. 
 

System monitoring goes off line 
multiple times within the first 24-36 
hours 
 

Normally due to automatic 
firmware updates 

► No action is required; the updates may 
require the system to restart occasionally 
once an update has been automatically 
downloaded. 
 

System monitoring has stopped 
 

Monitoring and ceased but 
system is still working   

► Restart the sonnen system 
 
► Restart the modem 
 
► Switch off and restart the meter power 
supply 
 
► Ensure the Modbus cable is screened 
and grounded at the meter If not then earth 
all additional cable into the negative 
terminal to reduce noise as this can 
interrupt the Ethernet port function. 
 

System monitoring does not show 
my map location 
 

Location of system on 
online User Portal will 
default to Germany   

► Please email 

[email protected]

 

with the unit serial number and system 
location for this to be amended manually. 
 

Daily values on the Smartphone App 
seem too high or wrong 

Values are inconsistent 
with previous values or 
expectation 

► The Smartphone App unlike graph 
display and the online User Portal show 
average values instead of instantaneous 
readings. These can take a while to settle 
down especially with a new installation. 
 

System shuts down within 180 
seconds of being initiated

 

Safety feature due to 
monitoring connection 
issue 

► Make sure that Batteries DC cables are 
connected correctly 
► Make sure that Battery BMS is 
connected correctly 
► Make sure that Battery voltage p/module 
is correct and each are within 1V of each 
other 
► Make sure that Overall connected 
battery voltage is correct 
► Make sure that Battery addresses are 
set correctly 
► Make sure that Battery Modbus address 
is set correctly 
► Make sure that the AC connection is 
wired correctly 
► Make sure that Correct AC phasing is 
wired on 3-phase (eco 8.03) systems 