0000 meet r1 c1

When appears a reading alarm (rising or falling setpoint) the relay permanently activated until occurs a manual 
forced or SMS.

Input 4a20mA: 

c1

acces code meet rNo 

relay

c1

È

È

È

When 

TELKAN 

receives the order, it returns an SMS to the sender with confirmation of the new configuration, if you want to override this SMS (saving money card that 

manages the 

TELKAN

) must only add an asterisk (*) at the end of each order (not for relay status query and History temperatures).

The programming is done via SMS messages through a mobile phone. It is imperative to introduce exactly the same characters as they are written in the description. Phones 

with call in hidden number identification can only send orders and can not receive confirmation messages.

To turns relay ON  (*)

acces code rNo relay on

È

È

0000 r1 on

Turns the relay on and returns a status message to the sender

acces code rNo relay on No minutes

È

È È

0000 r2 on 15

Turns the relay on for the number of minutes specified in the message and then switches it OFF. (Adjustable: 1 
...64 800 minutes.) This command returns two status messages to the sender: the first to confirming receipt of 
the command, and a second message when the relay status changes to OFF.

To turns relay OFF  (*)

acces code rNo relé off

È

È

0000 r1 off

Turns the relay off and returns a message to the sender indicating the new status.

Exemple of SMS

 

= 1 space

È

Timed relay activation  (*)

Log telephone number for receiving SMS   (*) 

To receive SMS alarm must register the phone number with the function inform on

acces code inform on

È

È

0000 inform on

Save the phone number that sent this order to send SMS alarm to occur. Save up to 4 phone numbers, then 
you have to clear before sending a new one.

Timed relay deactivation  (*)

Reset all phone numbers in memory for receiving SMS   (*)

acces code inform reset

È

È

0000 inform reset

Deletes ALL the phone numbers stored in memory for alarm notification via SMS.

USE SMS MESSAGES TO CHANGES SETTINGS

acces code = 

0000

 (from factory, change by personal code)

acces code rNo relay off No minutes

È

È È

0000 r2 off 15

Turns the relay OFF for the number of minutes specified in the message and then switches it ON. (Adjustable: 1 
...64800 minutes.) This command returns two status messages to the sender: the first to confirming receipt of 
the command,and a second message when the relay status changes to ON.

Change of acces code

acces code pass new code

È

È

0000 pass 1234

Changes the access code (from the factory default of 0000) and returns a confirmation message to the sender

Relays behaviors, MEET   (*)  

You can link any of the relays to any of the inputs (sensors, transducers, contact closure alarms, battery)

acces code meet

È

0000 meet 

It returns a message with the status of the function on/off and device is connected as the operation of the relay

acces code meet

rNo relay

a1

È

È

È

0000 meet r1 a1

When it detects an contacts alarm relay activates permanently until there is a forced manual or by SMS.

acces code meet

rNo relay

b1

È

È

È

0000 meet r2 b1

When it detects a change in power supply (battery to grid / network battery) activates the relay permanently 
until there is a forced manual or by SMS.

Remove phone numbers for receiving SMS  (*)

acces code inform off

È

È

0000 inform off

Delete the phone number you sent the order for receiving sms alarm.

List of number of phones that receive SMS  

acces code inform

È

Returns an SMS to the sender reporting phone numbers that will send the SMS at alarm temperature, contacts, 
failure of power supply in net

0000 inform

acces code meet

rNo relay

t1

È

È

È

0000 meet r1 t1

When it detects an temperature alarm (rising or falling humidity) activates the relay permanently until there is a 
forced manual or by SMS.

Battery: 

b1

Relays: 

r1, r2, r3, r4

Temperature probes: 

t1, t2, t3

Contact Alarms: 

a1, a2, a3

SMS estructure

acces code meet

rNo relay

off

È

È

È

0000 meet r1 off

The relay operation is independent. The relay is activated by SMS or manually pressing the front button 

TELKAN

Operative status  (*)

acces code alive No days

È

È

0000 alive 1

Sends a test message every number of hours configurated to communicate that status of device is operative (SIM 
has money and works correctly). If programmed to 0, the function is off. Range: 0 (off) ... 45 days.

acces code alive

È

0000 alive 

Sends a SMS with the time remaining for the next send of sms alive

Programm the sending of test message without SMS of confirmation

Example of order without return SMS of confirmation (adding * at the end of the SMS order)

0000 alive 1*

acces code alive No days*

È

È

IMPORTANT:  

to receive SMS alarm, alive and other than shipping immediately has to register the phone number on control with the function inform.

 (*) 

It means that this order has the option to override the confirmation message by adding an asterisk at the end of the message

Define a scale of values for c1  (*)

acces code scale c1 initial value final value

È

È È

È

0000 scale c1 0 1500

Sets the values for the minimum and maximum of the scale for the analog input C1

Units of measure for the scale of c1  (*)

acces code units magnitude

È

È

0000 units liters

With this SMS you can define what is being measured with the input c1 of 4a20mA. For example: 
liters, kg, humidity ...

acces code alarm c1 off

È

È È

0000 alarm c1 off

Deactivates the alarm function for c1 analog input and returns an SMS to confirm the new status.

acces code avg c1

È

È

0000 avg c1

Returns an SMS with the readings of: current, for the past 1 min, 4 mins, 15 mins, 1 hr and 4 hrs

acces code delay c1 minutes minutes

È

È È

È

0000 delay  c1 2  5

Delays on / off reading alarm (default 0, disabled = reported immediately). The same operation as 
the previous order.

Alarm reading

acces code scale c1 initial value

È

È È

È

0000 scale c1 0 1500 2

Sending  this  message  sets  the  beginning  and  end  of  the  scale  and  also  set  two  decimal.  In  the 
example would scale of 0-1500 and shows readings in 0.00 format

final value No decimals to show

È

acces code alarm c1 value for the scale

È

È È

0000 alarm c1 100

Activates  the  alarm  function and  defines  the  threshold  within  the  configured  scale  value  and 
returns an SMS to confirm the new status. 

If you also want to alert you when the alarm occurs it is 

necessary to send the order to inform on.

Status Query  

If you missed a call the number on the SIM, SMS returns a test

acces code test

È

0000 test

Send  an  SMS  to  the  sender  reporting  the  status  of  the  relay,  the  time  it  is  connected  (if 
programmed), status of the GSM signal 

TELKAN 

and current temperature.

Version

acces code version

È

0000 version

Send an SMS to the sender informing the program version, modem signal, voltage for the power 
supply (these values depending of battery charge & electric network) & status of PROMO function.

Alarm Settings Query

acces code alarm

È

Returns a text message informing the sender of the setting, on / off and values of the alarms for 
temperature, contacts failure of power supply in net..

Checking recent temperatures & readings

acces code avg t1

È

È

0000 avg t1

Returns an SMS with the current temperature and the average temperature for the past 1 min, 4 
mins, 15 mins, 1 hr and 4 hrs. If you have already sent a valid command from the same number, you 
can  obtain  the  status  by  phone.  The 

TELKAN 

hangs  up  and  sends  an  SMS  with  the  above 

temperature data.

0000 alarm

Alarm deactivation  (*)

acces code alarm a1 off

È

È È

0000 alarm a1 off

Deactivates the alarm function and returns an SMS to confirm the new status.

Alarm activation  (*)

acces code alarm a1 on

È

È È

0000 alarm a1 on

Activates the contact alarm function and returns an SMS to confirm the new status. 

If you also 

want to alert you when the alarm occurs it is necessary to send the order to inform on.

Alarm activation/deactivation delay  (*)

acces code delay a1 minutes minutes

È

È È

È

0000 delay  a1 2  5

Delays on / off contacts alarm (default 0, disabled = reported immediately). You can set a common 
value for  activation and deactivation (0000    delay    5)  or  different  in  each case, two  values of 
minutes: 0000  delay  5  10). Range (0 ... 240 minutes).

acces code delay b1 minutes minutes

È

È È

È

0000 delay  b1 2  5

Delays on / off failure of power supply alarm (default 0, disabled = reported immediately). The same 
operation as the previous order.

acces code delay t1 minutes minutes

È

È È

È

0000 delay  t1 2  5

Delays on / off temperature alarm (default 0, disabled = reported immediately). The same operation 
as the previous order.

acces code delay

È

0000 delay 

Returns an SMS to the sender informing of delays programmed to alarm temperature. for each of 
type alarm, temperature, contacts, failure of power supply...

Alarm contact

Alarm failure of power supply

Alarm temperature

acces code alarm b1 off

È

È È

0000 alarm b1 off

Deactivates the alarm function for failure of power supply and returns an SMS to confirm the new 
status.

acces code alarm t1 off

È

È È

0000 alarm t1 off

Deactivates the alarm function for temperature and returns an SMS to confirm the new status.

acces code alarm b1 on

È

È È

0000 alarm b1 on

Activates the alarm function for failure of power supply and returns an SMS to confirm the new 
status. 

If you also want to alert you when the alarm occurs it is necessary to send the order to inform 

on.

acces code alarm t1 temperaturE °C

È

È È

0000 alarm t1 45

Activates the Temperature alarm function, sets the temperature limit to that sent by the user and 
returns an SMS to confirm the new status. 

If you also want to alert you when the alarm occurs it is 

necessary to send the order to inform on.

To change SMS language

acces code lang No new language

È

È

0000 lang 0

Changes the language setting (default Spanish) to the selected language No: 0=Spanish, 1=English

Exemple of  SMS

Receiving messages Commercials   (*)  

from factory setting in on

acces code promo off

È

È

0000 promo off

Sets the control to delete all commercials messages received

acces code promo on

È

È

0000 promo on

The control sends at the telephone number registered in function inform, all received messages 
that start with text.