                SM2170B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page2

 

Brand 

SONBEST 

CO2 range 

0~5000ppm 

CO2 accuracy 

±

100ppm 

Communication Interface 

RS485 

Default baud rate 

9600 8 n 1 

Power 

DC9~24V 1A 

Running temperature 

-40~80° C 

Working humidity 

5%RH~90%RH 

        Product Size 

        Wiring instructions 

        Any incorrect wiring can cause irreversible damage to the product. Please carefully wire the cable as 

follows in the case of power failure, and then connect the cable to confirm the correctness and then use it 

again.   

ID 

Core color 

Identification 

Note 

Red 

V+ 

Power + 

Green 

V- 

Power - 

Yellow 

A+ 

RS485 A+ 

Blue 

B- 

RS485 B- 

                                     

        In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the 

core color is for reference. 

        Communication Protocol 

        The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands 

are hexadecimal data. The default device addr ess is 1 when the device is shipped, the default baud rate is 

9600, 8, n, 1   

Содержание SM2170B

Страница 1: ...MODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring carbon dioxide state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE Lora WIFI GPRS and other output methods Technical Parameters Technical parameter Paramete...

Страница 2: ...the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Green V Power 3 Yellow A RS485 A 4 Blue B RS485 B In the case of broken wires wire the wires as shown in the figure If the product itself has no leads the core color is for reference Communication Protocol The product uses R...

Страница 3: ...fy device address 1 Read or query device address If you don t know the current device address and there is only one device on the bus you can use the command FA 03 00 64 00 02 90 5F Query device address Device ID Function id Start Address Data Length CRC16 FA 03 00 64 00 02 90 5F FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 ...

Страница 4: ...from 9600 to 38400 ie changing the code from 3 to 5 the command is 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 Device ID Function id Start Address Target Baud Rate CRC16 01 03 00 66 00 01 64 15 Change the baud rate from 9600 to 38400 changing the code from 3 to 5 The new baud rate will take effect immediately at which point the device will lose its response and the baud rate of the device shoul...

Страница 5: ...e effect immediately after successful change Disclaimer This document provides all information about the product does not grant any license to intellectual property does not express or imply and prohibits any other means of granting any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes...

Отзывы: