10
Copyright © 2016 Somfy SAS. All rights reserved.
Do not install the Détecteur de fumée connecté :
• Outside
• In a location where it is difficult to hear the alarm (room with closed door)
• In a location where it is difficult to access the detector, in particular to carry out tests
• In a location where the temperature is below 4°C or above 45°C
• In a location where the humidity is below 10% or above 95% (bathroom, kitchen, laundry room, etc.)
• In a location affected by large and/or rapid variations in temperature, pressure or humidity
• In a location where the detector is exposed to direct sunlight
• In a dusty or dirty location (garage, workshop, etc.)
• In a location infested with insects
• In a location where smoke or fumes from the surrounding area could compromise the Détecteur de fumée connecté : kitchen, flue,
garages (exhaust gas), stove, boiler, combustion radiators, etc.
• Near to heating appliances, windows, ventilation outlets, air conditioning units, fans or any other equipment that could produce air
currents
• Near to a location which is warmer or cooler than the rest of the room (uninsulated walls, hatches, etc.)
Position the Détecteur de fumée connecté in accordance with the applicable building standards.
Ceiling installation:
• Install the detector on the ceiling in the centre of the room and at least 30 cm from corners,
walls, joists or other obstacles.
Wall installation:
• Install the detector on the wall, between 30 cm and 60 cm from the ceiling.
Sloping ceiling installation:
• Install the detector between 30 cm and 60 cm vertically from the highest point on the ceiling.
.
.
30 cm
30 cm
60 cm
30 cm
60 cm