Preserve heat
Set Timer...
Delay...
Temperature threshold...
Use function...
the Preserve heat function menu
On delay and vice versa. If you find that the function is still active even though there have been
sun for a while then decrease the Off delay and vice versa.
H
This function requires an outside temperature sensor. The
Preserve heat function is active
only in Automatic mode.
Using exterior solar protection: If there is any risk that the solar protection can
“freeze”, an exterior thermostat should be connected to e.g. the system’s external
lock input/s. The set point should be set just above the freeze point. Contact your solar
protection supplier for more consultation.
Preserve Heat parameters
Function
Range (Step)
Per Zone
Default
Advanced
Used
Yes/No
Yes
No
No
Threshold
-10 - +10C (1C)
Yes
+3C
No
Start time
00:00-23:59
Yes
00:00
No
Stop time
00:00-23:59
Yes
00:00
No
On Delay
0-30min
Yes
5min
Yes
Off Delay
0-30min
Yes
10min
Yes
Sun
About:
The Sun function is used to command the end products to specific position
when there is sun. Using this function helps to avoids over heating and glaring
situations inside the building. Sun function can only get active in Automatic mode.
Enable this function for each zone by selecting Yes in the “use function” parameter.
Active:
This function gets active when the sun intensity exceeds the On threshold for a certain
time period (On delay) and the solar protection will go down. When the sun intensity is lower
than the Off threshold for a certain time period (Off delay) then the function gets inactive and
the solar protection will be commanded to up position.