MBUS-RELA4 - User manual
Table 12 –
Continued from previous page
Byte no.
Size (bytes)
Value (HEX)
Description
47
1
20
Data information field extension (DIFE): tariff 2/relay 2
48
1
FD
Value information field (VIF)
49
1
1B
Value information field extension (VIFE): digital input
50
1
01
Value: read back state relay 2
51
1
81
Data information field (DIF): 8 bit integer
52
1
30
Data information field extension (DIFE): tariff 3/relay 3
53
1
FD
Value information field (VIF)
54
1
1B
Value information field extension (VIFE): digital input
55
1
00
Value: read back state relay 3
56
1
81
Data information field (DIF): 8 bit integer
57-58
2
80 10
Data information field extension (DIFE): tariff 4/relay 4
59
1
FD
Value information field (VIF)
60
1
1B
Value information field extension (VIFE): digital input
61
1
00
Value: read back state relay 4
62
1
04
Data information field (DIF): 32 bit integer
63
1
24
Value information field (VIF): operating time
64-67
4
38 03 00 00
Value: operating time since last start in seconds
68
1
01
Data information field (DIF): 8 bit integer
69
1
FD
Value information field (VIF)
70
1
17
Value information field extension (VIFE): Error flags
71
1
00
At present 0
72
1
0A
Data information field (DIF): BCD 4 digits
73
1
FD
Value information field (VIF)
74
1
0F
Value information field extension (VIFE): software version
75-76
2
10 01
Firmware version 1.10
77
1
0D
Data information field (DIF): variable length
78
1
FD
Value information field (VIF)
79
1
0C
Value information field extension (VIFE): model / version
80
1
0A
Length of the meter entry (variable length): 10
81-90
10
34 41 4C 45 52
Text: “MBUS-RELA4”
2D 53 55 42 4D
91
1
B7
Checksum (CS)
92
1
16
Stop character
Table 12: RSP_UD as response on REQ_UD2
This example contains the following values:
• Primary address: 1
• Secondary address (secondary ID): 01 00 00 34 = serial number 1000034
• Manufacturer ID: SLV
• Device version: 1
• Device type: switching element
• Sent state (relay 1-4): off, on, off, off
• Read back state (relay 1-4): off, on, off, off
• Operating time: 824 seconds (=
0x338
)
• Firmware version 1.10
The
Manufacturer ID
can be converted to a manufacturer code maintained by the
DLMS User Association
.
An overview can be found here: www.dlms.com/flag-id/flag-id-list
Page 20/21
UG_EN_MBUS-RELA4.pdf
Version: 1.3
Released
Frank Richter, 6 December 2022
© solvimus GmbH