SOLL AT EK
INTELLIGENT CONTROL S
Page 29
•
If Regulation probe reading >= HAt + HdF
•
Heater:
OFF
•
Resume normal operation
•
If Winter mode is enabled and activated, then defrost function will be disabled until the winter mode is
terminated.
•
When unit is in Winter mode and Regulation Probe is detected to be faulty, then unit will exit Winter mode and
resume working as normal mode.
8.13 AMBIENT CONDITION INTERACTION
Parameter Description
Units
Min
Max
An
Nominal Ambient condition
°C
0
90
AnA
Ambient interaction Enabled: No, Yes
NO / YES
An1
Ambient change threshold 1
°C
0
10
An2
Ambient change Threshold 2
°C
0
10
AS1
Regulation temperature limit change on An1
°C
-5
5
AS2
Regulation temperature limit change on An2
°C
-5
5
ALL
Lower Ambient Safety Limit
°C
-50
0
ALU
Upper Ambient Safety Limit
°C
0
80
Operation explanation:
•
Ambient Sensor temperature reading < An
•
Respective Set Point is used without any adjustment
•
Ambient Sensor temperature reading > An and =< An + An1
•
Respective Set Point (cut-out) and cut-in values (on any operational mode) are increased by AS1
•
Ambient Sensor temperature reading > An + An1 and =< ALU
•
Respective Set Point (cu-out) and cut-in values (on any operational mode) are increased by AS2
•
If Ambient Sensor reading < ALL
•
Compressor:
OFF
•
Evaporator fan resumes working according to section 2.5
•
Defrost function will be disabled
•
If Ambient Sensor reading >ALU
•
Compressor:
OFF
•
Evaporator fan:
Resumes working accordingly
•
Defrost function will be disabled
8.14 LEARNING ALGORITHM
Parameter Description
Units
Min
Max
dOt
Learning algorithm door operating duration
Sec
1
255
Operation explanation:
•
dOt: Accumulated time of door openings duration in order to register day mode operation.