3. Installation

3. Installation

.23.

.22.

3.4.2.1 DC connection high voltage danger notice

CAUTION 

RISK OF ELECTRIC SHOCK 

Do not touch an energized DC conductor.  There are high voltages present when PV modules 

are exposed to light causing a risk of death due to an electric shock from touching a DC 

conductor!

Only connect the DC cables from the PV module to the inverter as described in this manual.

CAUTION 

POTENTIAL DAMAGE TO THE INVERTER DUE TO OVERVOLTAGE 

The DC input voltage of the PV modules must not exceed the maximum rating of the inverter.  

(see section 10 “Specifications”)

Check the polarity and the open-circuit voltage of the PV strings before connecting the DC 

cables to the inverter.

Confirm proper string length and voltage range before connecting DC cable to the inverter. 

3.4.3 Connect grid side of inverter

       1).  Connect the three (3) AC conductors to the three (3) AC terminals marked “L1”, “L2” and 

             “L3”.Refer to local code and voltage drop tables to determine the appropriate wire size 

              and type.

       2).  Connect the grounding conductor to the terminal marked “PE” (protective earth, the 

             ground terminal).

Over-Current Protection Device (OCPD) for the AC side

To protect the inverter's AC connection line, we recommend installing a device for protection 

against over-current and leakage, with the following characteristics noted in Table 3.2: 

WARNING 

An over-current protection device must be used between the inverter and
the grid.

NOTE

Use AL-CU transfer (bi-metallic) terminal or

 

anti-oxidant

 

grease

 

with

 

aluminum

 

cables

 

and

 

terminals.

Table 3.2 Rating of grid OCPD

3.4.3.1 Connecting the inverter to the utility grid

All electrical installations must be carried out in accordance with the local standards and the 

National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. The 

AC and DC electric circuits are isolated from the enclosure. If required by section 250 of the 

National Electrical Code®, ANSI/NFPA 70, the installer is responsible for grounding the system.

The grid voltage must be within the permissible range. The exact operating range of the inverter 

is specified in section 10 “Specifications”.

Inverter

Rated 
voltage(V)

Rated output
current (Amps)

Current for protection 
device (A)

152.0/144.3

167.1/158.8

200

250

Solis-100K-5G

Solis-110K-5G

150.4

480

200

Solis-125K-HV-5G

220/380,230/400

220/380,230/400

Solis-50K-LV-5G

Solis-100K-5G-SA

131.2

157.5

220

200

200

200

250

Solis-60K-LV-5G

Solis-110K-5G-SA

220

220/380,230/400

220/380,230/400

167.1/158.8

152.0/144.3

152.0/144.3

167.1/158.8

200

250

S5-GC100K

S5-GC110K

150.4

480

200

S5-GC125K-HV

220/380,230/400

220/380,230/400

3.4.3.2 Wiring procedure

CAUTION

RISK OF ELECTRIC SHOCK. 

Prior to starting the wiring procedure, ensure 

that the three-pole circuit breaker is switched off and cannot be reconnected.

NOTE 

Damage or destruction of the inverter's electronic components due to 
moisture and dust intrusion will occur if the enclosure opening is enlarged.

CAUTION 

Risk of fire if two conductors are connected to one terminal. If a 
connection of two conductors to a terminal is made, a fire can occur. 
NEVER CONNECT MORE THAN ONE CONDUCTOR PER TERMINAL.

NOTE

Use M10 crimp terminals to connect to the inverter AC terminals

.

S5-GC50K-LV

131.2

157.5

220

200

200

S5-GC60K-LV

220

Содержание S5-GC100K

Страница 1: ...Binhai Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and conta...

Страница 2: ...onfiguration 32 6 Start and Shutdown 6 1 Start up procedure 6 2 Shutdown procedure 33 33 33 7 1 Main Menu 34 34 7 2 Information 4 1 RS485 and PLC communication connection 26 7 Normal operation 34 4 2...

Страница 3: ...ribution grid This manual covers the three phase inverter model listed below Solis 100K 5G Solis 110K 5G Solis 125K HV 5G HV S5 GC100K S5 GC110K S5 GC125K Solis 50K LV 5G Solis 60K LV 5G S5 GC50K LV S...

Страница 4: ...nal box to repackage the inverter seal with adhesive tape with the desiccant inside the box Store the inverter in a clean and dry place free of dust and dirt The storage temperature must be between 40...

Страница 5: ...RNING Risk of fire Despite careful construction electrical devices can cause fires Do not install the inverter in areas containing highly flammable materials or gases Do not install the inverter in po...

Страница 6: ...erminals communication waterproof connectors to prevent the cables from sagging and causing the waterproof connectors to loosen Tilt angle 15 Ground clearance 300mm 3 1 2 Installation environment requ...

Страница 7: ...d vertically The steps to mount the inverter are listed below 1 Refer to Figure 3 6 drill holes for mounting screws based on the hole diameter of bracket using a precision drill keeping the drill perp...

Страница 8: ...from vertical Figure 3 10 Wrong installation Angle The steps to mounted to the rack are listed below 3 Install mounting plate 1 Remove the bracket and fasteners from the packaging Mark the position f...

Страница 9: ...OFF 2 Switch the DC Isolator OFF 3 Connect the inverter to the grid 4 Assemble PV connector and connect to the Inverter Inverter design uses PV style quick connect terminal The top cover needn t be o...

Страница 10: ...nding 2 Prepare OT terminals M10 To effectively protect the inverter two grounding methods must be performed Connect the AC grounding cable Please refer to section 3 4 3 Connect the external grounding...

Страница 11: ...MAKE SURE the polarity of the PV array output conductors matches the DC and DC terminal labels before connecting these conductors to the terminals of the inverter 5 Measure PV voltage of DC input wit...

Страница 12: ...s Table 3 2 Rating of grid OCPD 3 4 3 1 Connecting the inverter to the utility grid All electrical installations must be carried out in accordance with the local standards and the National Electrical...

Страница 13: ...terminal block The torque is 10 20Nm Figure 3 27 Wiring with Neutral Solis 100 110 K 5G Solis 50 60 K LV 5G S5 GC 100 110 K S5 GC 50 60 K LV Figure 3 28 Wiring without Neutral Solis 125K HV 5G S5 GC1...

Страница 14: ...tween PLC communication and RS485 communication can be realized by flipping the switch on the communication board as indicated in figure 4 2 Only one communication method is available during operating...

Страница 15: ...ard be verified for the country of installation before commissioning The menu for changing the grid standard or for creating a custom standard is accessible as described in Section 6 7 and below WARNI...

Страница 16: ...d by the inverter see Specifications in section 10 may damage the inverter Although Solis inverters feature reverse polarity protection prolonged connection in reverse polarity may damage these protec...

Страница 17: ...ed DC POWER LED and LCD will be continuously lit 4 Solis inverters are powered from the DC side When the inverter detects DC power that is within start up and operating ranges the inverter will turn o...

Страница 18: ...verter App_Power Shows the apparent power of the inverter Work Mode Volt watt DRM NO 08 10 sec 10 sec Work Mode Shows current working mode DRM NO Shows DRM Number I_DC01 Shows input 01 current value I...

Страница 19: ...1 Alarm Message 2 Running message 3 Version 4 Daily Energy 5 Monthly Energy 6 Yearly Energy 7 Daily Records 8 Communication Data 9 Warning Message The following submenus are displayed when the Settin...

Страница 20: ...history of changing settings Only for maintance personel 7 Normal operation 7 Normal operation 7 4 3 Version The screen shows the model version of the inverter And the screen will show the software v...

Страница 21: ...1 1S Startup T 10 600S OV G F1 50 2 53Hz 60 2 63Hz OV G F1 T 0 1 9S OV G F2 51 53Hz 61 63Hz OV G F2 T 0 1 9S UN G F1 47 49 5Hz 57 59 5Hz UN G F1 T 0 1 9S UN G F2 47 59Hz 57 59Hz UN G F2 T 0 1 9S Resto...

Страница 22: ...DOWN key to move the cursor Press the UP key to revise the value Press the ENTER key to execute the setting Press the ESC key to return to the previous menu 7 5 4 Reset Password This function is used...

Страница 23: ...r the switch is open the inverter HMI will display Limit by DRM and the inverter output power will be limited to zero 1 Select Initial Settings 2 Select DRM and set it ON 7 5 10 HMI Update HMI Current...

Страница 24: ...l operation 7 Normal operation Figure 7 25 Selecting Fan Test displays the sub menu shown below Are you sure YES ENT NO ESC Fan Test is a factory test function Press the ENTER key to start the test Pr...

Страница 25: ...Normal operation Solis Three Phase Inverter does not require any regular maintenance However cleaning the dust on heat sink will help the inverter to dissipate the heat and increase its life time The...

Страница 26: ...all the time Can not start up 1 Check if the connector on main board or power board are fixed 2 Check if the DSP connector to power board are fixed 1 Check inverter surrounding ventilation 2 Check if...

Страница 27: ...he PV string current down below 0 5A Turn off the two DC switchs and fix the polarity issue Screen OFF with DC applied Inverter internally damaged 1 Do not turn off the DC switches as it will damage t...

Страница 28: ...rtz 45 55 or 55 65 2W Noise emission typical 65 dBA Intelligent redundant cooling Dimensions W H D Weight 1065 567 344 5mm 84kg Max DC input voltage Volts MPPT voltage range Volts Max input current Am...

Страница 29: ...nge Hertz 45 55 or 55 65 2W Noise emission typical 65 dBA Intelligent redundant cooling Dimensions W H D Weight 1065 567 344 5mm 84kg Max DC input voltage Volts MPPT voltage range Volts Max input curr...

Страница 30: ...5 2W Noise emission typical 65 dBA Intelligent redundant cooling Dimensions W H D Weight 84kg Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings n...

Страница 31: ...ntelligent redundant cooling IEC 61727 IEC 62116 C10 11 VDE 4105 IEEE 1547 Dimensions W H D Weight 84kg Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input...

Страница 32: ...IEC 61727 IEC 62116 C10 11 VDE 4105 IEEE 1547 Dimensions W H D Weight 84kg Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid v...

Страница 33: ...45 55 or 55 65 0 99 0 8 leading 0 8 lagging Noise emission typical 65 dBA Dimensions W H D Weight 1065 567 344 5mm 84kg Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT...

Страница 34: ...nce Belgium South Africa Italy UK UK Comments For German Low Voltage Grid For Polish Low Voltage Grid For Dutch Low Voltage Grid General EN50438 Requirement Possible to be used in Austria Cyprus Finla...

Отзывы: