![Solid State Cooling Systems THERMORACK 800 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/solid-state-cooling-systems/thermorack-800/thermorack-800_product-manual_1315386004.webp)
T
HERMO
R
ACK
800
T
HERMOELECTRIC
C
HILLER
52-13007-1
S
OLID
S
TATE
C
OOLING
S
YSTEMS
,
167
M
YERS
C
ORNERS
R
OAD
,
W
APPINGERS
F
ALLS
,
NY
12590
3
T
ELEPHONE
:
(845)
296-1300
F
AX
:
(845)
296-1303
WEB
:
WWW
.
SSCOOLING
.
COM
V
ERSION
M8
SAFETY
PRECAUTIONS
AND
SYMBOLS _________________________
Read the SDS for the coolant used and follow
all
safety precautions
listed in the SDS prior to removing coolant tubes or opening the fill
cap as this could result in contact with the coolant inside.
Caution! Risk of electric shock. Disconnect the power cord prior to
servicing. This includes changing a fuse or opening the cover for any
reason.
Earth Ground Safe operation of the ThermoRack 800 requires that
earth ground be connected to the IEC-320 C20 power cord supplied
with the system.
Note: Some internal components may be electrically live regardless of
ON/OFF switch position. For the safety of the operator, only trained
personnel may interact with internal components.
Caution! Heavy object. System weighs 55 lbs (25 kg). Two people
are required to lift.
CAUTION
Never disassemble the chiller as irreparable damage may occur.
Any attempt to open or repair the unit will void the warranty
Never store the chiller over 70 °C.
Never operate the chiller in ambient temperatures of 40 ºC or greater.
Never operate the chiller within 5 ºC of the coolant’s freezing point.
Always use only proper coolants as specified in manual. Solid State Cooling Systems
recommends Koolance LIQ-702CL-B (27% propylene glycol and water)
Never ship the chiller with coolant inside the liquid cold plate as freezing temperatures may be
encountered which would damage the unit. Always pump all coolant out of the chiller prior to
shipping.
Always match wetted materials (metal) to the wetted materials in your system. If your system
has aluminum cold plates/tubing, use the standard Oasis. If your system has copper cold
plates/tubing, select the Oasis copper models. Stainless steel may be used with either material.