Suspension for rigid ceiling installation
Suspension systems are required for the dry
mortarless installation of the fire damper with
mineral wool in ceiling slabs. Fire dampers can be
suspended from solid ceiling slabs using adequately
sized threaded rods. Load the suspension
system only with the weight of the fire damper.
Ducts must be suspended separately.
Installations
INSTALLATION
Damper blade must be closed during installation!
1. Suspension strut should be connected with drop
rods (8/10 mm) to the ceiling slab above. It is used
to support the damper and ease the installation.
2. If using L profile fixation, support steel C profile
with 50 mm high peace of aerated concrete or
similar rigid material. Not necessary if connecting
rods directly to damper.
3. Damper casing is fixed to suspended and
supported steel C profiles by two self tapping
screws 4.8 x 16 (make sure that it doesn’t
interfere with damper blade) with L profile
hanger (detail A) fixed to steel C profiles by
M8 screw and nut. Position of selftapping
screws is trough the middle of damper casing.
4. To finish the installation please follow the steps
(2. - 4.) from .
Test the operation of the damper blade!
27 mm
18 mm