18
| Round fire damper manual 02/2021
SOLID AIR ®
CLIMATE SOLUTIONS
•
T +31 598 36 12 21
•
www.solid-air.com
•
Rang
e
Supporting
construction
Wall
thickness
Supporting construction
details
Type of installation
Classification
Tested
underpressure
Details
Construction
type
Sealing
type
d100-
d800 mm
Rigid wall
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m
3
)
Reinforced concrete
(≥ 2200 kg/m
3
)
Gypsum plaster/mortar
EI 120 (ve i
↔
o)S
500 Pa
Mineral wool and cover
boards
EI 90 (ve i
↔
o)S
500 Pa
Fire Batt/Weichschott
300 Pa
Flexible wall
≥ 70 mm Gypsum blocks
(≥ 995 kg/m
3
)
Gypsum plaster/mortar and
cover boards
EI 120 (ve i
↔
o)S
500 Pa
≥ 100 mm Plasterboard
type A (EN520)
Gypsum plaster/mortar
EI 120 (ve i
↔
o)S
500 Pa
Mineral wool and cover
boards
EI 90 (ve i
↔
o)S
500 Pa
Fire Batt/Weichschott
EI 90 (ve i
↔
o)S
300 Pa
Floor/
ceiling
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m
3
)
Reinforced concrete
(≥ 2200 kg/m
3
)
Gypsum plaster/mortar
EI 120 (ho i
↔
o)S
500 Pa
Fire Batt/Weichschott
EI 90 (ho i
↔
o)S
300 Pa
APP I
NS
TALL
ATION FR
AME
d100-
d3
15 mm
Rigid wall
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m
3
)
Reinforced concrete
(≥ 2200 kg/m
3
)
Applique (installation frame)
EI 90 (ve i
↔
o)S
500 Pa
Flexible wall
≥ 70 mm Gypsum blocks
(≥ 995 kg/m
3
)
Applique (installation frame)
EI 90 (ve i
↔
o)S
500 Pa
≥ 100 mm Plasterboard
type A (EN520)
Applique (installation frame)
EI 90 (ve i
↔
o)S
500 Pa
MF1/ MF2 I
NS
TALL
ATION FR
AME
FDC25 MF1 d100-
d3
15 mm
FDC40 MF2 d355-
d800 mm
Rigid wall
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m
3
)
Reinforced concrete
(≥ 2200 kg/m
3
)
MF1 (installation frame)
MF2 (installation frame)
FDC25:EI 60 (ve i
↔
o)S
500 Pa
FDC40:EI 90 (ve i
↔
o)S
Flexible wall
≥ 70 mm Gypsum blocks
(≥ 995 kg/m
3
)
MF1 (installation frame)
MF2 (installation frame)
FDC25:EI 60 (ve i
↔
o)S
500 Pa
FDC40:EI 90 (ve i
↔
o)S
≥ 100 mm Plasterboard
type A (EN520)
MF1 (installation frame)
MF2 (installation frame)
FDC25:EI 60 (ve i
↔
o)S
500 Pa
FDC40:EI 60 (ve i
↔
o)S
MF2 I
NS
TALL
ATION FR
AME
FDC25 MF2 d100-
d3
15mm
FDC40 MF2 d355-
d800 mm
Flexible wall ≥ 90 mm Shaft wall (steel frame)
(type 98/48)
MF2 (installation frame)
FDC25:EI 60 (ve i
↔
o)S
500 Pa
FDC40:EI 60 (ve i
↔
o)S
ISO
VER
d100-
d6
30
mm (only
FDC40)
Flexible wall ≥ 100 mm Plasterboard
type A (EN520)
Remote from wall (Isover)
EI 60 (ve i
↔
o)S
300 Pa
Aerated concrete ( ≥ 550 kg/m3) or reinforced concrete
(≥ 2200 kg/m3) wall, more than 100 mm thick.
Gypsum blocks (≥ 995 kg/m3) wall, more than
70 mm thick.
Plasterboard wall, type A (EN520), more than
100 mm thick.
Aerated concrete ( ≥ 550 kg/m3) or reinforced concrete
(≥ 2200 kg/m3) ceiling / floor, more than 100 mm thick.
Gypsum plaster, mortar sealing or mortar
and cover boards.
Sealing with mineral wool and cover boards.
Sealing with mineral wool and fireproof
coating - FireBatt/Weichschott.
Applique kit installation.
MF1/MF2 kit installation.
Remote from wall installation.
Shaft wall, steel frame construction.
INSTALLATION
Check for more information about certificate installations in the declaration of performance:
Details