GR90, EV90, EV90P

ERV

MAINTENANCE

DIFFERENTIAL STATIC ACROSS CORE DSP VS. CFM

EV

90

, G

R90

DSP

0.10

0.20

0.30

Fresh Air (FA) CFM

42

84

127

Room Air (RA) CFM

42

84

127

DIFFERENTIAL STATIC ACROSS CORE DSP VS. CFM

EV

90P

DSP

0.10

0.20

0.30

Fresh Air (FA) CFM

58

115

173

Room Air (RA) CFM

58

115

173

The proper airflow range 
for the models are 40-110 
CFM.

 CAUTION

Make sure clean filters are 
installed before balancing 
air flow. Dirty or clogged 
filters reduce airflow 
through the unit.

 CAUTION

Keep your ERV performing at its best by cleaning it as described below.

5.1 TO CLEAN THE ENERGY EXCHANGE ELEMENT

  1. Remove the filters (see below). 
  2. Vacuum the exposed faces of the energy exchange core with a soft brush attachment. 
  3. After servicing the filters, re-install them (see below). 
  4.  Vacuum out dust from the rest of the unit case. Dust collects only on the entering faces 

of the energy exchange core. The interior of the energy exchange core stays clean even if 
the core faces are dust covered. The core flutes move the air in a laminar airflow such that 
particulate deposition is maintained at virtually nill.

5.0 MAINTENANCE

5.2

 

INSPECT AND CHANGE THE FILTERS REGULARLY 

Service filters every three months when the unit is in regular use or as needed to keep them 
reasonably clean. 
  1. Release cam latches and carefully swing access door open. Remove the door by sliding to 
      one side. 
  2. Remove filter clips. 
  3. Pull the filters out. 
  4. Vacuum with a hose attachment. 
  5. Re-install filters and filter clips, see Section 5.5 Service Parts. Orange side of filter should  
      face the core.
  6. Re-install door, and fasten cam latches.
The primary contact for replacement filters for your RenewAire unit is the installing contractor. 
As an alternative, you may wish to produce your own filters. Please follow these instructions:
Filters may be cut from a sheet or roll of ¾"–1" firm, spun polyester filter “hog hair” media or 
material, similar to the existing filter in the residential unit.
The size of each filter (2 required per unit) is as follows:

 EV90/GR90

 

9 ½" x 10 ½" 

 

EV90P  

21 ¾" x 10 ½"

Call your HVAC contractor or RenewAire for further information.

DO NOT WASH THE  

ENERGY EXCHANGE CORE.

Keep it away from water 
or fire to avoid damaging 
it. Always handle the core 
carefully.

 CAUTION

Risk of Fire, Electric Shock, 

or Injury.

u

   Before servicing or  

cleaning the unit, unplug 

the line cord. 

u

   Make sure unit is not 

running before opening its 

door. Blower wheels are 

sharp and can cut.

u

   Do not disable the  

interlock switch: it is there 

for your safety.

 WARNING

NOTE: The filters 
should be replaced 
after they have 

been cleaned several 
times.

NOTE: Filters must 
be used or the 
face of the energy 

exchange core will become 
blocked by dust and 
reduce unit efficacy. The 
filters supplied in the unit 
are usually able to keep 
the energy exchange core 
clean for many months. 
Finer filters can be used 
but must be cleaned more 
often.

Содержание RenewAire ERV Series

Страница 1: ...tage Controls Line Cord Model GR90 Galvanized Case Line Voltage No Line Cord Model EV90P High Performance Unit Painted Case Low Voltage Controls Line Cord GR90 EV90 EV90P GR EV SERIES ERV Installation Operation and Maintenance Manual ...

Страница 2: ...ith all applicable building health and safety code requirements 5 Connect this unit only to a 120 VAC grounded receptacle protected by a 15 or 20 amp circuit breaker Do not remove the unit s line cord 6 Do not install unit or controls where they can be reached from a tub or shower 7 This unit must be properly ducted to the outdoors 8 Outside air inlet for this unit must be located away from source...

Страница 3: ...Aire DO NOT SCALE DRAWING REMOVE ALL BURRS BREAK SHARP EDGES APPLICABLE STANDARDS DIM AND TOL ANSI Y14 5 TITLE DRAWING NO SCALE REVISION SHEET DATE BY KMC 04 30 15 3 DEG 005 015 63 Z ULTI 3000 WHITE SEE MATERIAL KMC MF LABEL SERIAL EV90 9 20 12 140088_000_D02 1 1 A 1 OF 1 MATERIAL FINISH LINEAR HOLE SIZE SURFACE FINISH UNLESS OTHERWISE SPECIFIED DIMENSIONS AND TOLERANCES ARE IN INCHES 4510 Helgese...

Страница 4: ...8 Minimum Service Area Door can be Removed from Hinges 22 1 4 Minimum Service Area 21 1 4 Door Swing 2 5 8 7 8 Typ 21 7 8 Case 6 Nominal Typ 8 Nominal Typ 25 1 2 Overall with Hanging bracket Formed Inlet Ring LEFT VIEW FRONT VIEW RIGHT VIEW TOP VIEW Model GR90 Drawing Type Unit Dimension Version JUN18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fres...

Страница 5: ... Typ 24V AC Control Terminal 11 3 4 Typ 5 3 4 Typ 6 1 4 Typ 22 1 4 Minimum Service Area 10 1 8 Minimum Service Area Door can be Removed from Hinges 21 1 4 OA EA RA FA Door Swing 34 Line Cord Pressure Ports 4 Typ 23 3 4 Overall 11 5 8 Case 21 7 8 Case 6 Nominal Typ 8 Nominal Typ 7 8 Typ 2 5 8 25 1 2 Overall with Hanging Bracket Formed Inlet Ring LEFT VIEW FRONT VIEW RIGHT VIEW TOP VIEW Model EV90 D...

Страница 6: ... AC Control Terminal 6 1 4 Typ 11 3 4 Typ 5 3 4 Typ OA EA RA FA 34 Line Cord Pressure Ports 4 Typ 23 3 4 Overall 23 5 8 Case 22 1 4 Minimum Service Area Door can be Removed from Hinges 22 1 4 Minimum Service Area Door Swing 8 Nominal Typ 6 Nominal Typ 7 8 Typ 2 5 8 21 7 8 Case 25 1 2 Overall with Hanging Bracket Formed Inlet Ring LEFT VIEW FRONT VIEW RIGHT VIEW TOP VIEW Model EV90P Drawing Type Un...

Страница 7: ...E AIR AND EXHAUST AIR DUCTS 14 3 3 INSIDE DUCTWORK SYSTEM FOR WALL MOUNTED UNITS ONLY 14 3 4 INSTALLING RETURN AIR DUCTS 14 3 5 CONTROLS 15 3 5 1 Installing Controls 15 4 0 OPERATION 16 4 1 STARTING UP THE UNIT 16 4 2 VERIFYING UNIT PERFORMANCE 16 4 2 1 Airflow 16 4 2 2 Use Static Taps to Measure Airflow Rates 16 4 2 3 Use Damper to Balance Airflow to Desired Rates 16 4 3 MEASURING AIRFLOW 17 4 4 ...

Страница 8: ...r Supply 12 Figure 2 4 2 Funace Return Air back into Return Air 12 Figure 2 4 3 RFurnace Return Air back into Supply Air EV90 P only 12 Figure 3 1 0 Mounting the ERV to a Stud Wall EV90 P only 13 Figure 3 5 0 Typical Control Schematic EV90 P only 15 Figure 4 2 0 Damper Installation 16 Figure 4 4 0 Airflow Diagram EV90 P 17 Figure 5 5 0 Service Parts EV90 P 19 TABLE OF CONTENTS TABLE OF ILLUSTRATIO...

Страница 9: ...ot the function of an ERV 1 2 2 When Should You Use Your ERV Use your ERV when windows are closed and you need to ventilate When the outdoor air is warmer or cooler than comfortable the ERV will allow a quieter more secure home with the windows closed and will also save energy 1 2 3 Using an ERV with Air Conditioning An ERV works very well with air conditioning because its enthalpy transfer energy...

Страница 10: ...ervice Area Door can be Removed from Hinges 21 1 4 OA EA RA FA Door Swing 34 Line Cord Pressure Ports 4 Typ 23 3 4 Overall 11 5 8 Case Typ Typ FRONT VIEW RIGHT VIEW TOP VIEW ABBREVIATIONS EA Exhaust Air to outside OA Outside Air intake RA Room Air to be exhausted FA Fresh Air to inside INSTALLATION ORIENTATION Unit may be installed in any orientation NOTE 1 UNLESS OTHERWISE SPECIFIED DIMENSIONS AR...

Страница 11: ...eas may be dampered so that they can be shut off when not in use A central location such as a hallway is also acceptable but won t clear humidity and odors from baths and kitchens as rapidly Locate stale air return grilles RA near the ceiling on inside walls Stale air returns are usually easiest to install in interior partitions u STALE AIR RETURN GRILLE SIZES u BATHROOM 4 x 10 or 6 x 10 40 to 60 ...

Страница 12: ... may be operated separate from furnace blower FIGURE 2 4 0 SEPARATE ROOM AIR PICK UP FRESH AIR TO FURNACE RETURN AIR TRUNKLINE www renewaire com 800 627 4499 support renewaire com NOTE The furnace blower must be operated any time the ERV is operated Use furnace fan on continu ous low speed or optional FM control to cycle furnace fan on ERV FIGURE 2 4 2 FURNACE RETURN AIR BACK INTO RETURN AIR www r...

Страница 13: ...ure the screws which you must supply are properly selected for the loads and substrate involved u MOUNTING THE EV90 P TO A STUD WALL Mount unit using supplied hanging bracket kit as described for mounting to concrete foundation wall u SUSPENDING THE EV90 P FROM FLOOR JOISTS OR TRUSSES The unit may be screwed directly to joists or trusses using the hanging bracket and integral flange Mount as descr...

Страница 14: ...is securely fastened and sealed to the duct collar DO NOT USE MORE FLEX DUCT THAN NECESSARY Flex duct is much more resistant to airflow than rigid duct longer runs of flex duct will reduce the ventilation performance of your system Stretch flex duct and avoid sharp bends Ducts connecting the unit to the outside must be well insulated Vapor barrier is required on both inside and outside of the insu...

Страница 15: ...nnecting or servicing controls WARNING 3 5 1 Installing Controls The EV90 P is offered with a control board for connection to external controls The GR90 runs continuously whenever power is supplied to it u Optional Controls RenewAire offers a variety of controls specifically designed to work with the EV90 P These include PTL a two wire percentage timer FM a six wire percentage timer that will inte...

Страница 16: ...manently install flow measuring stations and manometers These can also be used to determine when filters should be cleaned or changed 4 2 2 Use Static Taps to Measure Airflow Rates See Differential Static Across Core tables in Section 4 4 on page 19 4 2 3 Use Damper to Balance Airflow to Desired Rates if necessary The ERV s blower motors are well suited for volume control by dampers on the inlet o...

Страница 17: ... Air OA port and the low pressure side to the Fresh Air FA port u To read SCFM of Room Air RA install the high pressure side of your measuring device to the Room Air RA port and the low pressure side to the Exhaust Air EA port u If gauge drops below zero reverse tubing connections u Use the reading displayed on your measurement device to cross reference the CFM output using the conversion chart NO...

Страница 18: ... open Remove the door by sliding to one side 2 Remove filter clips 3 Pull the filters out 4 Vacuum with a hose attachment 5 Re install filters and filter clips see Section 5 5 Service Parts Orange side of filter should face the core 6 Re install door and fasten cam latches The primary contact for replacement filters for your RenewAire unit is the installing contractor As an alternative you may wis...

Страница 19: ...n changing filters 1 Remove paper leaves etc from inlet and outlet screens 2 Inspect for insect nests 5 5 SERVICE PARTS ewaire com 800 627 4499 support renewaire com FIGURE 5 5 0 SERVICE PARTS EV90 P In the unlikely event that you need assistance from the factory for a specific issue make sure that you have the information called for in the Unit Information page in the front of this manual The per...

Страница 20: ...liability derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of static plate core technology in North America RenewAire is the largest ERV producer in the USA We re committed to sustainable manufacturing and lessening our environmental footprint and to that end our Waunakee WI plant is 100 powered by wind turbines The facility is also on...

Отзывы: