DECOR-100 CHZ

These models are provided with an 
electronic humidistat which can be 
adjusted between 60, 70, 80 or 90% 
RH (relative humidity) and with an 
automatic run-on-timer, adjustable 
between 5, 10 or 20 minutes.  Both 
humidistat and timer adjustments 
can be made using the correspond-
ing adjustment dials without the 
need to remove the front grille of 
the fan.

HUMIDISTAT

The desired humidity level is se-
lected by means of an adjustment 
dial (6) located on the side of the 
fan casing.  The corresponding 
relative humidity level, 60-70-80 or 
90%, is then visually indicated via 
one of four neon lights.  All models 
are factory set as standard to a 90% 
relative humidity level.

OVER-RUN TIMER

All models include an over-run timer 
which enables the fan to continue 
to operate after the primary switch 
has been disconnected (switched 
off).  The over-run time should be 
set in accordance with local and 
national building code regulations 
and also with respect to the pro-
portion of humidity encountered. 
For brief periods of operation the 
over-run time should be set to the 
minimum period of 2 minutes.  For 
prolonged periods of operation the 
over-run time should be set to the 
maximum period of 20 minutes. 
This will ensure the most ef

¿

 cient 

extraction of the humid air whilst 
saving time on fan operation.

Operation

Case

1: Automatic operation(

¿

 g.5)

In automatic operation, the humi-
distat causes the extractor to oper-
ate automatically when the humidity 
level in the room is higher than the 

pre-set level. The extractor will 
stop automatically when the hu-
midity drops below the selected 
level and after the selected pe-
riod set on the over-run timer.

Case

2: Automatic operation as 

in case (1) but with the facility to 
override the humidistat by means 
of the light switch (

¿

 g.4),  when 

the humidity level in the room is 
lower than the selected level. In 
this case, the extractor continues 
to operate for the selected period 
of time (over-run timer) after the 
switch light has been switched off.

 If the period of operation is 

less   than 50 seconds then the 
overrun timer will not operate.

If the period of operation is more
than 50 seconds then the over-
run timer will operate in accord-
ance to the pre-set time period.

ATTENTION: When the humid-
ity rate is above the selected 
value, the automatic option 
takes precedence over the 
manual and the unit cannot 
then be switched off using a 
switch.

Maintenance

The extractor fan only requires 
periodical cleaning using a cloth 
lightly impregnated with a soft 
detergent.

After Sales Service

We recommend you not to try to 
dismantle or remove any other 
parts than those mentioned as 
any tampering would automati-
cally cancel the S&P guarantee. 
If you detect any fault, contact 
your S&P dealer.

S&P reserves the right to alter 
speci

¿

 cations without notice.

Содержание DECOR-100

Страница 1: ...OR 100 VISUAL Instrucciones de uso User instructions Notice d utilisation Montageanweisungen Montage Gebruiksaanwijzing Instruções de utilização Libretto istruzioni Användar instruktion Instrukcja obslugi ...

Страница 2: ......

Страница 3: ......

Страница 4: ...Fig 1 Fig 2 1 3 2 6 5 4 ...

Страница 5: ...Fig 3 L s ...

Страница 6: ...Fig 4 Fig 5 ...

Страница 7: ...ll or ceiling of 105 mm dia If the unit is to be installed with individual ducting use a standard 100 mm dia duct Undo the two grille xing screws 2 and then the corresponding front grille 1 Ensure that there are no obstruc tions to the airflow and that the impeller turns freely Fix the extractor to the wall in such a way that it is not distorted in order to avoid unnecessary noise generation or pr...

Страница 8: ...eration Operation Case 1 Automatic operation g 5 In automatic operation the humi distat causes the extractor to oper ate automatically when the humidity level in the room is higher than the pre set level The extractor will stop automatically when the hu midity drops below the selected level and after the selected pe riod set on the over run timer Case 2 Automatic operation as in case 1 but with th...

Страница 9: ...3 Soler Palau Sistemas de Ventilación S L U C Llevant 4 08150 Parets del Vallès Barcelona ESPAÑA Tel 93 571 93 00 Fax 93 571 93 01 Fax int 34 93 571 93 11 e mail consultas solerpalau com Web www solerpalau com MÃ01 ...

Отзывы: