PVI 10KW / PVI 13KW / PVI 15KW Installation and Operation Manual
DOC-020028 rev 028
25
5.
Reset SRV
Settings are cleared to factory defaults. Caution: This will also
clear Revenue-grade KYZ counters.
KYZ Meter Menu
Displays KYZ readings, if installed. See Solrenview manual for KYZ installation.
1.
AC Energy
Cumulative energy count
2.
AC Power
Power reading
3.
Pulse Weight
Multiplier to convert pulses to WH for display. F
For example Pulse Weight = 10 WH
1 pulse = 10 WH
5 Trouble Shooting
The PVI 10KW / PVI 13KW / PVI 15KW is designed, produced and rigorously tested for long life
and reliability in a wide range of climate conditions, voltage and power levels.
With a properly shipped, sited, mounted, wired and tested installation, the integrated PVI 10KW /
PVI 13KW / PVI 15KW inverter unit should give many years of trouble-free and maintenance-free
service.
The following trouble shooting information will help in the event that the inverter does not
function, stops functioning or does not provide full performance.
WARNING:
Before attempting to open disconnects or the main enclosure, read the
entire manual, especially warning messages and “Opening The Main Enclosure” later
in this section. Only qualified personnel should attempt to open any of these
enclosure doors or do any service or troubleshooting.
PV system not functioning
•
Check LED indicator status
•
Check connection to grid, 3-phase AC voltage & CLOCKWISE phase rotation (with meter)
•
Check DC (PV) string connections or main PV feed conductor connections
•
Verify PV voltage range including hot module temperature MPP voltage and cold module
temperature, open circuit voltage (OCV)
•
Contact installer or Solectria Renewables if malfunction persists
•
If contacting Solectria Renewables for assistance, please provide part number, serial
number, short description of problem (LED indicator status, when problem started, how
often problem occurs, under what conditions the problem occurs) and information on PV
modules (string layout, number of modules per string, number of strings, module model
and part number, output power, short-circuit current and open circuit voltage)
Some specific problems that can be identified quickly
GFDI Problem: If the LED indicators show a ground fault problem but the GFDI fuse is not blown
then a ground fault in PV array or wiring must be found. If the LED indicators show that the