83 • Control Keypad
________________________________________________________________________________________________
FAULT PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section
6.5.1 page 56 for changing mode)
Display and Default
Values
Range Description
Remarks
STORE ENABLE
FAULT PARAMETERS
Same as STORE ENABLE
MAIN PARAMETERS on page 71.
7.7.8
I/O Programming Parameters – Page 7
I/O PROGRAMMING
PARAMETERS
Displays in MAXIMIZED MODE only
6.5.1 page 56 for changing mode)
Display and Default
Values
Range Description
Remarks
PROG. INPUT # 7
RESET
RESET;
SLOW SPEED;
ENERGY SAVER;
Sets terminal
7 function
Refer to section
7.7.8.1 on page 84.
PROG. INPUT # 8
DUAL ADJUSTMENT
DUAL ADJUSTMENT;
SLOW SPD REVERSE;
RESET;
Sets terminal
8 function
Refer to section
7.7.8.1 on page 84.
FAULT RELAY TYPE
FAULT
FAULT,
FAULT – FAIL SAFE
Sets FAULT
RELAY mode
of operation.
When configured to FAULT the
internal relay is energized upon fault.
When configured to FAULT-FAIL
SAFE the relay is
de
-energized upon
fault. In this mode, while normal
operation, the fault relay is energized.
Relay will also
de
-energize upon
control power outage.
IMM/ S.PIN RELAY
IMMEDIATE
IMMEDIATE/
SHEAR-PIN.
Sets RVS-
DN’s IMM/
S.PIN
RELAY
mode of
operation.
When configured to IMMEDIATE the
IMM/ S.PIN RELAY energizes at the
start signal after the programmed
RELAY ON DELAY time has elapsed.
It de-energizes at the end of the
deceleration time (if any) after the
programmed RELAY OFF DELAY
time has elapsed.
RELAY ON DELAY
0 SEC.
0 – 3600SEC. (when
IMM/ S.PIN RELAY
Is programmed as
IMMEDIATE);
0.0 – 5.0SEC. (when
IMM/ S.PIN RELAY
Is programmed as
SHEAR PIN)
Sets RVS-
DN’s IMM/
S.PIN
RELAY
on delay
time.
When configured to SHEAR PIN the
IMM/ S.PIN RELAY energizes when a
O/C-SHEAR PIN fault occurs after the
programmed RELAY ON DELAY
time has elapsed. It de-energizes after
the O/C-SHEAR PIN fault is cleared
and after the programmed RELAY
OFF DELAY time has elapsed.
RELAY OFF DELAY
0 SEC.
0 – 3600SEC. (when
IMM/ S.PIN RELAY
Is programmed as
IMMEDIATE);
0.0 – 5.0SEC. (when
IMM/ S.PIN RELAY
Is programmed as
SHEAR PIN)
Sets RVS-
DN’s IMM/
S.PIN
RELAY
off delay time
For more information regarding the
O/C-SHEAR PIN parameter refer to
section