4 • Technical Data 

________________________________________________________________________________________________ 

3.

 

TECHNICAL DATA 

3.1

 

Introduction 

The RVS-AX electronic soft starter incorporates six thyristors (Three phase control) to start a three-phase 
squirrel cage induction motor and an internal bypass (Internal bypass in RVS-AX31A and higher).  
By supplying a slowly increasing voltage, it provides soft start and smooth stepless acceleration, while drawing 
the minimum current necessary to start the motor. 
A Soft Stop feature can be enabled when the Ramp-Down potentiometer is adjusted. When used, upon stop 
Signal, motor's voltage is slowly reduced to zero. 
The RVS-AX incorporates a built in motor protection of Overload protection and Phase loss protection. 
The RVS-AX incorporates an internal protection to protect its heatsinks from over heating. 
No control voltage is required to operate the RVS-AX. 
 

3.2

 

Rating and frames sizes 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

3.3

 

Starter Selection 

Select the starter according to motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if the 
motor will not be fully loaded). 
The RVS-AX   is designed to operate under the following maximum conditions: 
 

Ambient 

Temperature 

[

0

C] 

Starting Current 

[A] 

Acceleration Time 

[sec] 

40 

300%xIn 

30  

350%xIn 

20  

400%xIn 

5  

 
Max. starts per Hour: four (4) starts per hour at maximum ratings and up to 10 starts per hour at light load 
applications (consult factory). 
 

Note

For very frequent starts (inching applications) the inching current should be considered as the Full Load 
Current (FLC) (consult factory). 

RVS-AX    

model 

FLC 

[A] 

Dimensions 

WxHxD 

[mm] 

Weight 

[kg] 

E

O

A Re

la

y

 

Faul

t R

el

ay

 

Int

er

na

bypass

 

RVS-AX  8 

120x232x105 

2.6 

 

 

No 

RVS-AX   17 

17 

120x232x105 

2.6 

 

 

No 

RVS-AX  31 

   31 

120x232x105 

2.6 

 

 

 

RVS-AX   44 

44 

120x232x105 

2.6 

 

 

 

RVS-AX   58 

58 

129x275x185 

 

 

 

RVS-AX  72 

72 

129x275x185 

 

 

 

RVS-AX  85 

85 

120x380x185 

8.4 

 

 

 

RVS-AX  105 

105 

120x380x185 

8.4 

 

 

 

RVS-AX  145 

145 

172x380x195 

11.8 

 

 

 

RVS-AX  170 

170 

172x380x195 

11.8 

 

 

 

Notes:

 

 

(

) – Standard 

 

 

Refer to section 

 

on page 11 for detailed dimensions.

 

Содержание RVS-AX

Страница 1: ...RVS AX Instruction and Commissioning Manual www solcon com RVS AX Analog Low Voltage Soft Starter 8 170 A 220 600V Low Voltage Analog Soft Starter Ver 1009...

Страница 2: ...3 Heatsink over temperature protection 6 3 6 4 Fault Logic and Reset Circuits 7 3 7 Starter selection tables for various voltage ratings 7 3 7 1 Ordering Information 8 4 Recommended Wiring Schemes 9 4...

Страница 3: ...liance with IEC 947 4 2 for class A equipment 2 Use of the product in domestic environments may cause radio interference in which case the user may be required to employ additional mitigation methods...

Страница 4: ...e RVS AX 3 2 Rating and frames sizes 3 3 Starter Selection Select the starter according to motor s Full Load Ampere FLA as indicated on its nameplate even if the motor will not be fully loaded The RVS...

Страница 5: ...inal is of no use Leave this terminal not connected 3 4 5 End Of Acceleration terminals 5 6 Voltage free N O 8A 250VAC 1800VA max The contact closes after the time adjusted on the Ramp Up potentiomete...

Страница 6: ...ase Loss The protection becomes operational when the starter is energized It protects the motor from single phasing It will trip the starter when one phase is missing for more than 1 sec When this pro...

Страница 7: ...e upstream contactor Mains voltage will be disconnected thus resetting the RVS AX and the motor will restart instantaneously see Fault Resetting 3 7 Starter selection tables for various voltage rating...

Страница 8: ...44 58 72 85 105 145 170 Mains Voltage Specify Description 230 220 240 Vac 10 15 400 380 415 Vac 10 15 440 440 Vac 10 15 480 460 500 Vac 10 15 600 575 600 Vac 10 15 Options Specify Description 0 No op...

Страница 9: ...g Notes WARNINGS When mains voltage is connected to the RVS AX full voltage may appear on the starter load terminals Therefore for isolation purposes it is necessary to connect an isolating device bef...

Страница 10: ...AX 17 2 000 6 6 URS 45 RVS AX 31 3 000 6 6 URS 63 RVS AX 44 6 000 6 6 URB 100 RVS AX 58 12 000 6 6 URB 150 RVS AX 72 18 000 6 6 URB 160 RVS AX 85 40 000 6 6 URD 200 RVS AX 105 60 000 6 6 URD 250 RVS A...

Страница 11: ...11 Dimensions ________________________________________________________________________________________________ 5 DIMENSIONS RVS AX 8 17 31 44 Note Mains voltage terminals 16mm2 RVS AX 58 72...

Страница 12: ...12 Dimensions ________________________________________________________________________________________________ RVS AX 85 105 RVS AX 145 170...

Страница 13: ...elow the starter for suitable airflow It is recommended to mount the starter directly on the rear metal plate for better heat dissipation Do not mount the starter near heat sources Surrounding air tem...

Страница 14: ...igned for the higher heat dissipation Internal enclosure heating can be reduced through the use of additional ventilation 6 4 1 44BHeat dissipation during RUN of RVS AX8A and RVS AX17A No internal byp...

Страница 15: ...ometers settings Potentiometer Range Description Motor FLC 50 100 The adjustment allows easy setting of the RVS AX current level automatically adjusting current based functions Overload Current Limit...

Страница 16: ...s highest current during starting Range is 100 400 of FLC as set on motor s FLC adjustment Too high of a setting will allow higher currents to be drawn from mains resulting in faster acceleration Too...

Страница 17: ...RESET button Green On Will lit when Mains voltage is connected to the starter Yellow Ramp Up Down Will lit during soft start and soft stop process indicating that motor supply voltage is ramping up or...

Страница 18: ...isolating device before upstream the starter 2 Power factor correction capacitors must not be installed on starters load side When required install capacitors on starter s line side 3 Before starting...

Страница 19: ...ter line terminals On LED will light 4 Apply Start command Motor starts to turn shortly after Start Initial inrush current or mechanical shock is too high Increase Initial Voltage and start again Decr...

Страница 20: ...moothly decreasing to the operating current High inertia loads crushers centrifuges mixers etc In these cases actual current is at Current limit setting in part of the starting time Current Limit set...

Страница 21: ...e overload level and thermal register has filled up Check FLA FLC and Overload settings check motor current wait at least 15 minutes to let motor and starter cool down before restarting Phase Loss LED...

Страница 22: ...Model Number And Build Options Example 170 400 8 S RVS AX _ _ _ _ _ _ __ _ Serial Number Purchasing Date Sale Installation Date Failure Date Draw one line diagram Draw control diagram Define time of...

Страница 23: ...the starter after the fault has been removed Indications Indication lights LEDs ON Green Lights when three phases are connected to the RVS AX Ramp Up Ramp Down Yellow Lights upon start signal or durin...

Страница 24: ...________________________ Mechanical Shock resistance 8 gn Conforming to EN 60947 4 2 Vibration resistance 2 gn Conforming to EN 60947 4 2 Output relay End of Acceleration Contact N O 8 A 250 V Fault C...

Отзывы: